Date Text
2005-12-20 00:00:00******** PROVISO **************
  
 1)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL EGRESS CORRIDORS
 AND STAIRWAYS.
 PLEASE SEE NFPA-101 7.8 WHICH REQUIRES A
 MININUM OF 10FT CANDLES UNDER NORMAL
 POWER.
 PLEASE SEE 7.9 WHICH ALLOWS A DECREASE
 TO 1FT CANDLE UNDER EMERGENCY POWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ALONG WITH ANY OTHER REVISIONS
 BEFORE ANY ROUGH ELECTRICAL INSPECTION
 IS CALLED IN.
  
 IF THERE ARE NAY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-19 00:00:00IN ELEC FOR REVIEW,
  
 **** PASSED, PENDING THE FOLLOWING ***
  
 NEED TO VERIFY LICENSE WITH STATE.
 THE NUMBER 3298 IS A ARCHITECT BUS
 NUMBER AND THE CERTIFICATE OF
 AUTHORIZATION NUMBER WHICH IS STILL
 COMING UP ON STATE WEBSITE APPEARS TO BE
 8338WHICH IS WHAT IS LISTED FOR THE
 FIRM LICENSED UNDER THE BOARD OF
 PROFESSIONAL ENGINEERS.
  
 NEED TO HAVE ENGINEER SIGN NEW SHEETS
 THE SAME AS PREVIOUS PLANS. APPEARS TO
 BE MISSING LAST NAME.