Plan Review Notes For Permit 05030119 |
Permit Number |
05030119 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-12-20 00:00:00 | ******** PROVISO ************** | | | | 1)NOTE: PLEASE PROVIDE COMPLETE | | PHOTOMETRICS FOR ALL EGRESS CORRIDORS | | AND STAIRWAYS. | | PLEASE SEE NFPA-101 7.8 WHICH REQUIRES A | | MININUM OF 10FT CANDLES UNDER NORMAL | | POWER. | | PLEASE SEE 7.9 WHICH ALLOWS A DECREASE | | TO 1FT CANDLE UNDER EMERGENCY POWER. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW ALONG WITH ANY OTHER REVISIONS | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | IS CALLED IN. | | | | IF THERE ARE NAY QUESTIONS, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | 2005-12-19 00:00:00 | IN ELEC FOR REVIEW, | | | | **** PASSED, PENDING THE FOLLOWING *** | | | | NEED TO VERIFY LICENSE WITH STATE. | | THE NUMBER 3298 IS A ARCHITECT BUS | | NUMBER AND THE CERTIFICATE OF | | AUTHORIZATION NUMBER WHICH IS STILL | | COMING UP ON STATE WEBSITE APPEARS TO BE | | 8338WHICH IS WHAT IS LISTED FOR THE | | FIRM LICENSED UNDER THE BOARD OF | | PROFESSIONAL ENGINEERS. | | | | NEED TO HAVE ENGINEER SIGN NEW SHEETS | | THE SAME AS PREVIOUS PLANS. APPEARS TO | | BE MISSING LAST NAME. |
|