2006-12-17 11:13:43 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | ARCHITECTURAL REVISION SUBMITTED ON 10/26/06. | | | | SHEETS A-4.01, A-4.02 AND A-4.03 CANNOT BE STAMPED AS | | SUBMITTED SO THEY HAVE BEEN SEPARATED AND ALL THREE | | COPIES RETURNED.ALL OTHER REVISED SHEETS HAVE BEEN | | STAMPED AND ONE COPY RETAINED FOR THE CITY FILE COPY. | | SEE COMMENT AND PROVISO BELOW. | | | | 1) THE SUBMITTED COPIES OF SHEETS A-4.01, A-4.02 AND | | A-4.03 ARE MISSING THE GUARDRAIL AND HANDRAIL DESIGN | | CRITERIA NOTES THAT WERE ON THE BOTTOM RIGHT CORNER OF | | EACH SHEET.ALSO, THE SUBMITTED COPY OF SHEET A-4.01 | | IS NOW MISSING NOTES FROM THE WEST PORTICO ELEVATION | | AND THE WEST PORTICO FLOOR PLAN (CAD LAYER NOT | | PRINTED???) | | | | 2) --PROVISO-- | | SHEETS A-1.01, A-1.02, A-1.03 AND A-1.04, WALL TYPE 18 | | SHALL HAVE 3/4" THICK PORTLAND CEMENT PLASTEROVER | | SELF-FURRING METAL LATH ON BOTH SIDES AS STATED IN THE | | U.L. DIRECTORY FOR THE SPECIFIED U.L. DESIGN NO. U484 | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | |
|