Date |
Text |
2005-11-18 00:00:00 | ************ UNSAT ************ |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| PLEASE ALSO SEE NEW NOTES. |
| |
| ************************************** |
| |
| 1)NOTE: NOTE #1 NO. PLEASE PROVIDE ALL |
| LIGHT POLE/LIGHT FIXTURE WIND LOADING |
| INFORMATIONFOR REVIEW AT THIS TIME. |
| PLEASE SEE MIN FBC 140 MPH. |
| IF "SITE LIGHTING" WIND LOAD INFORMATION |
| AND FIXTURE INFORMATION IS NOT PROVIDED |
| AT THIS TIME, A SEPARATE PERMIT MAY BE |
| APPLIED FOR AT A LATER DATE. |
| INFORMATION STILL DO NOT SEEM TO BE |
| SUBMITTED AND RESPONSE LTR MENTIONS THIS |
| SHOULD BE DONE BY CONTRACTOR. |
| PLEASE KNOW, IF THIS INFORMATION SI NOT |
| DONE A THIS TIME, PLEASE REMOVE AND NOT |
| PLANS THAT ALL SITE-LIGHTING SHALL BE |
| UNDER A SEPARATE PERMIT, PLANS AND FEES. |
| |
| 2)NOTE: NOTE #2, NO, PLEASE SEE A |
| CERTIFICATE OF AUTHORIZATION NUMBER WAS |
| ADDED TO THE TITLE BLOCK FOR EACH TRADE |
| SHEET, HOWEVER PLEASE SEE PRINT OUT |
| ATTACHED FROM THE DEPARTMENT OF BUSINESS |
| AND PROFESSIONAL REGULATION (DBPR) WHICH |
| SHOWS THE CA # WHICH IS SHOWN ON TITLE |
| BLOCK LISTED FOR A COMPLETELY DIFFERENT |
| COMPANY. PLEASE VERIFY AND ADJUST #. |
| THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADES WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| 3)NOTE: NOTE #3 OK. |
| |
| 4)NOTE: NOTE #4 OK. NOTE, RESPONSED |
| LETTER MENTIONS THIS WAS NOT CLEAR, |
| HOWEVER THE ITEM WHICH APPEARED TO BE A |
| "PANEL" IN ROOM 317 WALL WAS REMOVED. |
| |
| 5)NOTE: NOTE #5, OK. 0. |
| |
| 6)NOTE:NOTE #6, NO, PLEASE SUBMIT ALL |
| INFORMATION ON FIRE PUMP/ FIRE PUMP |
| CONTROLLER. |
| PLEASE SUBMIT MANUFACTURES SPEC/CUT |
| SHEETS FOR BOTH. |
| PLEASE SEE NO SUBMITTIALS/SPECS/ CUT |
| SHEETS COULD BE LOCATED. |
| SERVICE ENTRNCE RATED ETC |
| PLEASE SEE NFAP-70 695, NFPA-20 10.4.2.1 |
| AND 10.4.2.2,10.1.2.5.1,230.76,230.79 |
| ETC WHICH NEEDS TO BE VERIFIED BY SPEC |
| SHEETS ALSO. |
| PLEASE LABEL TYPE OF BRKER FOR OCP AT |
| GEN AND BRKR DISCONNECT FOR FIRE PUMP. |
| IS THE BRKR TYPE MAG ONLY? |
| PLEASE KNOW: IF ALL OF THE ABOVE |
| INFORMATION IS NOT SUBMITTED ALL WOULD |
| BE REQUIRED UNDER SEPARATE PERMIT, PLANS |
| AND FEES. |
| PLEASE ALSO SEE THAT NO INFORMATION WAS |
| SUBMITTED FOR FUEL TANK, SIZE, LISITNG |
| ETC. |
| PLEASE SEE NFPA-20 WHICH REQUIRES A |
| MININUM OF 8HRS. 9.6,9.6.2.2 |
| |
| 7)NOTE: NOTE #7 OK. |
| |
| 8)NOTE: NOTE#8 OK.L |
| |
| 9)NOTE: NOTE #9 YES/NO,PLEASE SEE |
| SPECIFIC INFORMATION FOR TYPE AND SIZE |
| OF GEN IS INIDICATED ON PLANS, HOWEVER |
| PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| FOR GEN/ ATS/ GEN SUB-BASE FUEL TANKS |
| ETC. |
| PLEASE SEE PREVIOUS NOTE WITH RESPECT TO |
| FUEL TANK AND RUNNING LOAD AND HRS. |
| PLEASE SEE ATS FEED AND OCP IS NOW SHOWN |
| AT 200A'S. PLEASE SEE RISER DIAGRAM |
| STILL SHOWS PANEL "EM" AS 100A WHEN |
| PANEL SCHEDULE FOR EM HAS BEEN INCREASED |
| TO 150AS'. |
| PLEASE ALSO SEE PANEL CR IS STILL SHOWN |
| AT 125A ON RISER , YET CR PANEL SCHEDULE |
| SHOWS 150A'S. |
| |
| 10)NOTE: NOTE #10 PLEASE SEE 695.3, |
| NFPA-20 9.3.2.2.3.2(B) THE MAIN OR ANY |
| OTHER POWER SUPPLY MEANS OF |
| DISCONNECT/OCP FOR FIRE PUMP SHOULD NOT |
| BE LOCATED IN THE SAME ROOM AS NORMAL |
| MAINS OR POWER. ANY FIRE/EXPOSION THAT |
| MAY AFFECT THE ABILITY TO POWER FIRE |
| PUMP OR ANY POSSIBLE DISRUPTION IN AN |
| INADVERTANT SHUTTING DOWN OF MAINS OR |
| EQUIPMENT. |
| PLEASE FIND THE SPACE NEEDED FOR THIS OR |
| THE POSSIBILTY OF GENERATOR CONTAINING |
| TWO BREAKERS FOR POWER FEEDS. |
| |
| 11)NOTE:NOTE#11 OK. |
| |
| 12)NOTE: NOTE #12 NO,PLEASE SEE NOTE #1 |
| ON E4.10 ELECTRICAL NOTES MENTIONS, |
| "MAIN CIRCUIT BREAKERS IN PANELS MDLP1, |
| MDAH, AND MDH BOARDS SHALL BE "GROUND |
| FAULT PROTECTED"?? |
| PLEASE VERIFY THIS ? PLEASE SEE |
| 240.13,230.95 ETC WHEN GROUND FAULT |
| PROTECTION IS REQUIRED. THIS IS STILL IN |
| QUESTION. PLEASE EXPLAIN IN RESPONSE |
| LTR AS TO THE RATIONALE FOR REQUIRING |
| THESE MAINS TO BE GF PROTECTED. |
| |
| 13)NOTE: NOTE #13 NO, PLEASE SHOW LOAD |
| CALCULATIONS, PLEASE SHOW PER 220.3 |
| ,220.10, 220.11 ,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| REQUESTED ON PREVIOUS REVIEW. |
| PLEASE SEE RESPONSE MENTIONS LOAD |
| CALCUALTIONS ON EACH PANEL, HOWEVER SOME |
| PANELS WERE REVISED TO SHOW SOME |
| MODIFICATION, BUT NOT FULL LOAD |
| CALCULATIONS. |
| PLEASE ALSO SEE A LOAD CALCULATION FOR |
| MAIN SERVICES ARE NOT CLEAR WHERE THESE |
| ARE LOCATED. |
| |
| 14)NOTE: NOTE #14 NO,PLEASE SHOW OR NOTE |
| ALL TRACK LIGHTING CALCULATIONS PER |
| 220.12 |
| REQUESTED ON PREVISOU REVIEW AND FIRST |
| REVIEW. |
| RESPONSE LTR MENTIONS CORRECT VA FOR TRK |
| LTS CIRCUITS, HOWEVER THIS INFORMATION |
| AND/OR LOADS COULD NOT BE FOUND ON |
| PLANS. |
| |
| 15)NOTE: NOTE #15 OK. |
| |
| 16)NOTE: NOTE #16 OK. |
| |
| 17)NOTE: NOTE #17 YES, HOWEVER PLEASE |
| SEE THE NOTES BELOW. |
| PLEASE KNOW THE FOLLOWING MAY BE SET UP |
| AS A "PROVISO", BUT MAY BE ADDRESSED NOW |
| SINCE PLANS ARE CMOING BACK FOR OTHER |
| COMMENTS. |
| PLEASE PROVIDE PHOTOMETRICS FOR |
| COORIDORS AND EGRESS STAIRS PER 7.8.1.3. |
| PLEASE SEE NFPA-101 WHICH NOW REQUIRES |
| 10FT CANDLES IN STAIR AREAS. |
| THIS WAS IN AFFECT AS OF JAN 1ST, 2005. |
| PLEASE SEE THAT A BATTERY BACK UP |
| FIXTURE OF SOME TYPE WILL ALSO BE |
| REQUIRED IN STAIRS TO PROVIDE A MIN OF 1 |
| FT CANDLE UNDER EMERGENCY CONDITIONS. |
| ALTERNATING CIRCUITING IS ALREADY SHOWN |
| FOR STAIRWELLS, HOWEVER AS REFERENCED LS |
| 101 7-9.2.2(2) THE SHUTTING DOWN OF A |
| SINGLE MEANS OF DISCONNECT UNDER ME |
| POWER OR TRIPPING OF EM MAIN WILL LEAVE |
| EGRESS AREAS IN TOTAL DARKNESS. |
| PLEASE KNOW THAT A BATTERY BACK UP LT |
| FIXTURE WILL BE REQUIRED IN EELECTRICAL |
| RM, ELEVATOR MACH RM, AND FIRE PUMP RM. |
| |
| 18)NOTE: NOTE #18 OK. |
| |
| *** PLEASE KNOW, ONLY REQUIREMENTS OF |
| NOTE:17 MAY BE DONE AS A "PROVISO". |
| |
| PLEASE SEE POSSIBLE NOTES FROM OTHER |
| REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SEE THERE MAY BE FURTHER COMMENTS |
| SINCE NOT ALL INFORMATION WAS SUBMITTED |
| FOR REVIEW. |
| |
| PLEASE REVMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STMAPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
2005-11-17 00:00:00 | PLANS IN ELECTRICAL FOR REVIEW. |