Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop E
Sequence Number 3
Notes
Date Text
2005-11-18 00:00:00************ UNSAT ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES.
  
 **************************************
  
 1)NOTE: NOTE #1 NO. PLEASE PROVIDE ALL
 LIGHT POLE/LIGHT FIXTURE WIND LOADING
 INFORMATIONFOR REVIEW AT THIS TIME.
 PLEASE SEE MIN FBC 140 MPH.
 IF "SITE LIGHTING" WIND LOAD INFORMATION
 AND FIXTURE INFORMATION IS NOT PROVIDED
 AT THIS TIME, A SEPARATE PERMIT MAY BE
 APPLIED FOR AT A LATER DATE.
 INFORMATION STILL DO NOT SEEM TO BE
 SUBMITTED AND RESPONSE LTR MENTIONS THIS
 SHOULD BE DONE BY CONTRACTOR.
 PLEASE KNOW, IF THIS INFORMATION SI NOT
 DONE A THIS TIME, PLEASE REMOVE AND NOT
 PLANS THAT ALL SITE-LIGHTING SHALL BE
 UNDER A SEPARATE PERMIT, PLANS AND FEES.
  
 2)NOTE: NOTE #2, NO, PLEASE SEE A
 CERTIFICATE OF AUTHORIZATION NUMBER WAS
 ADDED TO THE TITLE BLOCK FOR EACH TRADE
 SHEET, HOWEVER PLEASE SEE PRINT OUT
 ATTACHED FROM THE DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION (DBPR) WHICH
 SHOWS THE CA # WHICH IS SHOWN ON TITLE
 BLOCK LISTED FOR A COMPLETELY DIFFERENT
 COMPANY. PLEASE VERIFY AND ADJUST #.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK. NOTE, RESPONSED
 LETTER MENTIONS THIS WAS NOT CLEAR,
 HOWEVER THE ITEM WHICH APPEARED TO BE A
 "PANEL" IN ROOM 317 WALL WAS REMOVED.
  
 5)NOTE: NOTE #5, OK. 0.
  
 6)NOTE:NOTE #6, NO, PLEASE SUBMIT ALL
 INFORMATION ON FIRE PUMP/ FIRE PUMP
 CONTROLLER.
 PLEASE SUBMIT MANUFACTURES SPEC/CUT
 SHEETS FOR BOTH.
 PLEASE SEE NO SUBMITTIALS/SPECS/ CUT
 SHEETS COULD BE LOCATED.
 SERVICE ENTRNCE RATED ETC
 PLEASE SEE NFAP-70 695, NFPA-20 10.4.2.1
 AND 10.4.2.2,10.1.2.5.1,230.76,230.79
 ETC WHICH NEEDS TO BE VERIFIED BY SPEC
 SHEETS ALSO.
 PLEASE LABEL TYPE OF BRKER FOR OCP AT
 GEN AND BRKR DISCONNECT FOR FIRE PUMP.
 IS THE BRKR TYPE MAG ONLY?
 PLEASE KNOW: IF ALL OF THE ABOVE
 INFORMATION IS NOT SUBMITTED ALL WOULD
 BE REQUIRED UNDER SEPARATE PERMIT, PLANS
 AND FEES.
 PLEASE ALSO SEE THAT NO INFORMATION WAS
 SUBMITTED FOR FUEL TANK, SIZE, LISITNG
 ETC.
 PLEASE SEE NFPA-20 WHICH REQUIRES A
 MININUM OF 8HRS. 9.6,9.6.2.2
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE#8 OK.L
  
 9)NOTE: NOTE #9 YES/NO,PLEASE SEE
 SPECIFIC INFORMATION FOR TYPE AND SIZE
 OF GEN IS INIDICATED ON PLANS, HOWEVER
 PLEASE SUBMIT MANUFACTURE SPEC SHEETS
 FOR GEN/ ATS/ GEN SUB-BASE FUEL TANKS
 ETC.
 PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 FUEL TANK AND RUNNING LOAD AND HRS.
 PLEASE SEE ATS FEED AND OCP IS NOW SHOWN
 AT 200A'S. PLEASE SEE RISER DIAGRAM
 STILL SHOWS PANEL "EM" AS 100A WHEN
 PANEL SCHEDULE FOR EM HAS BEEN INCREASED
 TO 150AS'.
 PLEASE ALSO SEE PANEL CR IS STILL SHOWN
 AT 125A ON RISER , YET CR PANEL SCHEDULE
 SHOWS 150A'S.
  
 10)NOTE: NOTE #10 PLEASE SEE 695.3,
 NFPA-20 9.3.2.2.3.2(B) THE MAIN OR ANY
 OTHER POWER SUPPLY MEANS OF
 DISCONNECT/OCP FOR FIRE PUMP SHOULD NOT
 BE LOCATED IN THE SAME ROOM AS NORMAL
 MAINS OR POWER. ANY FIRE/EXPOSION THAT
 MAY AFFECT THE ABILITY TO POWER FIRE
 PUMP OR ANY POSSIBLE DISRUPTION IN AN
 INADVERTANT SHUTTING DOWN OF MAINS OR
 EQUIPMENT.
 PLEASE FIND THE SPACE NEEDED FOR THIS OR
 THE POSSIBILTY OF GENERATOR CONTAINING
 TWO BREAKERS FOR POWER FEEDS.
  
 11)NOTE:NOTE#11 OK.
  
 12)NOTE: NOTE #12 NO,PLEASE SEE NOTE #1
 ON E4.10 ELECTRICAL NOTES MENTIONS,
 "MAIN CIRCUIT BREAKERS IN PANELS MDLP1,
 MDAH, AND MDH BOARDS SHALL BE "GROUND
 FAULT PROTECTED"??
 PLEASE VERIFY THIS ? PLEASE SEE
 240.13,230.95 ETC WHEN GROUND FAULT
 PROTECTION IS REQUIRED. THIS IS STILL IN
 QUESTION. PLEASE EXPLAIN IN RESPONSE
 LTR AS TO THE RATIONALE FOR REQUIRING
 THESE MAINS TO BE GF PROTECTED.
  
 13)NOTE: NOTE #13 NO, PLEASE SHOW LOAD
 CALCULATIONS, PLEASE SHOW PER 220.3
 ,220.10, 220.11 ,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 REQUESTED ON PREVIOUS REVIEW.
 PLEASE SEE RESPONSE MENTIONS LOAD
 CALCUALTIONS ON EACH PANEL, HOWEVER SOME
 PANELS WERE REVISED TO SHOW SOME
 MODIFICATION, BUT NOT FULL LOAD
 CALCULATIONS.
 PLEASE ALSO SEE A LOAD CALCULATION FOR
 MAIN SERVICES ARE NOT CLEAR WHERE THESE
 ARE LOCATED.
  
 14)NOTE: NOTE #14 NO,PLEASE SHOW OR NOTE
 ALL TRACK LIGHTING CALCULATIONS PER
 220.12
 REQUESTED ON PREVISOU REVIEW AND FIRST
 REVIEW.
 RESPONSE LTR MENTIONS CORRECT VA FOR TRK
 LTS CIRCUITS, HOWEVER THIS INFORMATION
 AND/OR LOADS COULD NOT BE FOUND ON
 PLANS.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 YES, HOWEVER PLEASE
 SEE THE NOTES BELOW.
 PLEASE KNOW THE FOLLOWING MAY BE SET UP
 AS A "PROVISO", BUT MAY BE ADDRESSED NOW
 SINCE PLANS ARE CMOING BACK FOR OTHER
 COMMENTS.
 PLEASE PROVIDE PHOTOMETRICS FOR
 COORIDORS AND EGRESS STAIRS PER 7.8.1.3.
 PLEASE SEE NFPA-101 WHICH NOW REQUIRES
 10FT CANDLES IN STAIR AREAS.
 THIS WAS IN AFFECT AS OF JAN 1ST, 2005.
 PLEASE SEE THAT A BATTERY BACK UP
 FIXTURE OF SOME TYPE WILL ALSO BE
 REQUIRED IN STAIRS TO PROVIDE A MIN OF 1
 FT CANDLE UNDER EMERGENCY CONDITIONS.
 ALTERNATING CIRCUITING IS ALREADY SHOWN
 FOR STAIRWELLS, HOWEVER AS REFERENCED LS
 101 7-9.2.2(2) THE SHUTTING DOWN OF A
 SINGLE MEANS OF DISCONNECT UNDER ME
 POWER OR TRIPPING OF EM MAIN WILL LEAVE
 EGRESS AREAS IN TOTAL DARKNESS.
 PLEASE KNOW THAT A BATTERY BACK UP LT
 FIXTURE WILL BE REQUIRED IN EELECTRICAL
 RM, ELEVATOR MACH RM, AND FIRE PUMP RM.
  
 18)NOTE: NOTE #18 OK.
  
 *** PLEASE KNOW, ONLY REQUIREMENTS OF
 NOTE:17 MAY BE DONE AS A "PROVISO".
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SEE THERE MAY BE FURTHER COMMENTS
 SINCE NOT ALL INFORMATION WAS SUBMITTED
 FOR REVIEW.
  
 PLEASE REVMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
2005-11-17 00:00:00PLANS IN ELECTRICAL FOR REVIEW.