2005-09-08 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 7/22/05: |
| |
| 11) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.SUBMITTAL OF SOME DOCUMENTS |
| FORBUILT-UP COAL TAR ROOFING SYSTEM, |
| DOORS AND WINDOWS IS NOTEDBUT THE |
| FOLLOWING MUST BE ADDRESSED. |
| A) KOPPERS (COAL TAR) BUILT-UP |
| ROOFING.MARK PAGE 6 OF EACH COPY OF |
| THE SUBMITTED PRODUCT TO SHOW WHICH OF |
| THE MAXIMUM DESIGN PRESSURE OPTIONS IS |
| APPLICABLE TO THIS PROJECT. SEE ITEM (F) |
| BELOW. |
| B) WINDOWS/DOORS.PER THE |
| DESIGN/PROJECT TEAM REQUEST, A SEPARATE |
| PERMIT APPLICATION WILL BE REQUIRED FOR |
| ANY NEW WINDOWS AND EXTERIOR DOORS NOT |
| COVERED IN THE ITEMS (C) THROUGH (E) |
| BELOW. |
| C) EXTERIOR DOORS.THE ARCH ALUMINUM |
| DOCUMENT SUBMITTED FOR NEW ENTRY DOOR |
| #101 IS NOT A PRODUCT APPROVAL AND SO |
| DOES NOT ADDRESS THE COMMENT FROM THE |
| PREVIOUS REVIEW (SEE 'NOTE' BELOW).AS |
| AN EXAMPLE OF WHAT IS REQUIRED REFER TO |
| THE SUBMITTED ROOF PRODUCT APPROVAL. |
| D) MULLIONS.NEW WINDOW TYPES E, G, |
| J, K, L, R, S ON SHEET A8.01 ALL REQUIRE |
| VERTICAL AND/OR HORIZONTAL MULLIONS. |
| DETAIL 1M ON SHEET A-8.03 DOES NOT SHOW |
| A STRUCTURAL MULLION.EITHER STRUCTURAL |
| MULLION DETAILS OR A MULLION PRODUCT |
| APPROVAL ARE REQUIRED. |
| E) DOUBLE HUNG WINDOWS.THE SUBMITTAL |
| OF HURRICANE TEST LAB INC TEST REPORTS |
| IS NOTED BUT THIS IS NOT A PRODUCT |
| APPROVAL AND SO DOES NOT ADDRESS THE |
| COMMENT FROM THE PREVIOUS REVIEW (SEE |
| 'NOTE' BELOW).AS AN EXAMPLE OF WHAT IS |
| REQUIRED REFER TO THE SUBMITTED ROOF |
| PRODUCT APPROVAL.ALSO, THE TEST |
| REPORTS ARE FOR WINDOWS THAT ARE 48-3/4" |
| WIDE.SHEET A-8.01 SHOWS THAT THE |
| PROPSED WINDOWS ARE UPTO 5'-0" WIDE AND |
| SO OUTSIDE THE SCOPE OF THE SUBMITTED |
| TEST REPORTS. |
| F) FBC 1606.1THE CALCULATED |
| PRESSURES FOR EACH WINDOW, EXTERIOR DOOR |
| AND THE ROOF MUST BE STATED ON THE PLANS |
| FOR COMPARISON WITH THE MAXIMUM DESIGN |
| PRESSURES IN THE ABOVE-MENTION PRODUCT |
| APPROVALS. |
| |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| (IF YOU FIND THAT THE QUOTED WEB PAGE IS |
| NO LONGER AVAILABLE, PLEASE INFORM THE |
| PLAN REVIEWER) |
| |
| 19) FBC 1403SHEETS A-4.01 TO A-4.04, |
| WALL DETAILS.THIS COMMENT HAS STILL |
| NOT BEEN ADDRESSED.THE SUBMITTED |
| COMMENT RESPONSE LETTER MAKES NO |
| STATEMENT ABOUT THIS COMMENT.SUBMIT |
| DETAILS TO SHOW MEANS OF RESTRAINT FOR |
| THE FACE BRICK VENEER AND LIMESTONE |
| CORNICE, FRIEZE, ARCHITRAVE, PEDIMENTS, |
| PANELS, BELTS AND BANDS. |
| |
| 23) FBC 1608.2.2GUARDRAIL STRENGTH. |
| ADDITION OF A NOTE TO THE PLANS IS NOTED |
| BUT IT CAN BE INTERPRETED INCORRECTLY |
| BECAUSE THE STATEMENT "(UNLESS NOTED |
| ABOVE)" WAS OMITTED, SEE CAPITALIZED |
| TEXT BELOW.EACH GUARDRAIL SHALL |
| BE DESIGNED AND CONSTRUCTED FOR A |
| CONCENTRATED LOAD OF 200 LB APPLIED IN |
| ANY DIRECTION AT THE TOP OF THE |
| GUARDRAIL, A CONCENTRATED HORIZONTAL |
| LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA |
| AT ANY POINT, AND A LINE LOAD OF 50 PLF |
| APPLIED HORIZONTALLY AT THE REQUIRED |
| GUARDRAIL HEIGHT WITH A SIMULTANEOUS |
| LINE LOAD OF 100 PLF APPLIED VERTICALLY |
| DOWNWARD ON THE TOP OF THE GUARDRAIL. |
| THESE LOADS SHALL NOT BE APPLIED |
| SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT |
| SHALL BE APPLIED INDIVIDUALLY TO PRODUCE |
| MAXIMUM STRESS IN EACH OF THE COMPONENTS |
| OR SUPPORTS.AMEND THE NOTE ON THE |
| PLANS. |
| |
| 24) FBC 1608.2.1THIS COMMENT HAS NOT |
| BEEN ADDRESSED.THE REQUIREMENTS FOR |
| HANDRAILS ARE DIFFERENT TO THOSE FOR |
| GUARDRAILS.EACH HANDRAIL SHALL BE |
| DESIGNED AND CONSTRUCTED FOR A |
| CONCENTRATED LOAD OF 200 LB AND A LINE |
| LOAD OF 50 PLF.THESE LOADS SHALL NOT |
| BE APPLIED SIMULTANEOUSLY BUT SHALL BE |
| APPLIED INDIVIDUALLY AT ANY POINT, AND |
| IN ANY DIRECTION, TO PRODUCE MAXIMUM |
| STRESS IN EACH OF THE COMPONENTS OR |
| SUPPORTS.AMEND/ANNOTATE THE PLANS. |
| |
| 25) FBC 3003.4SHEET A-6.11STRETCHER |
| ACCESSIBLE ELEVATOR.CONTRARY TO THE |
| COMMENT RESPONSE LETTER THE DETAILS/NOTE |
| ADDED TO THE PLANS DO NOT ADDRESS THIS |
| COMMENT.ELEVATOR NUMBER 144 SHALL BE |
| IDENTIFIED, BY SIGNAGE, AS STRETCHER |
| ACCESSIBLE.ANNOTATE THE PLANS TO |
| DEMONSTRATE COMPLIANCE |
| |
| 28) FBC* 105.13.1SPECIAL INSPECTOR. |
| THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE STRUCTURAL INSPECTION |
| PLAN ON SHEET S-1.00A IS NOTED, AS ARE |
| THE COMMENT RESPONSE LETTER DATED |
| 9/29/05 AND DAVID LOWE'S LETTER DATED |
| 6/29/05 BUT NO SPECIAL INSPECTOR |
| AGREEMENT HAS BEEN SUBMITTED.SUBMIT A |
| SPECIAL INSPECTOR AGREEMENT WITH THE |
| ORIGANAL SIGNATURES (AND SEALS WHERE |
| APPROPRIATE) OF THE OWNER, THRESHOLD |
| INSPECTOR, JOB INSPECTOR, CONTRACTOR AND |
| ENGINEER. |
| |
| 31)FBC 11-4.13.6SHEET A-0.10DOOR |
| TO THE MENS RESTROOM 106.THE SWING |
| DIRECTION OF THIS DOOR HAS BEEN CHANGED |
| SINCE THE LAST REVIEW.THE DOOR MUST |
| NOW BE MOVED TO THE SOUTH SO THAT THERE |
| IS MIN. 18" CLEARANCE BETWEEN THE STRIKE |
| EDGE OF THE DOOR AND THE ADJACENT WALL |
| RETURN. (FBC FIGURE 11-25). |
| |
| 32) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS, TO FORM A SET OF |
| 'OLD/VOID SHEETS', FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |