2005-07-18 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: THE COMMENT NUMBER |
| SHALL REMAIN THE SAME TO AVOID CONFUSION |
| 1. ALL SHEETS SHALL BE SIGNED, SEALED, & |
| DATED. ALL SHEETS SHALL CONTAIN A TITLE |
| BLOCK WITH ALL REQUIRED INFORMATION AND |
| LICENCES. FAC 61G1-16.004 & FS 481.219. |
| FS481.2055. - SEE SHTTES L1 THRU L6 AND |
| IRR-1 THRU IRR-3. |
| 6. SUBMIT A DETAIL SHOWING COMPLIANCE |
| WITH 11-4.15.2 SPOUT HEIGHT, 11-4.15.3 |
| SPOUT LOCATION, 11-4.15.4 CONTROLS, AND |
| 11-4.15.5 CLEARANCES/CLEAR FLOOR SPACE. |
| ALSO FOR THOSE WHO HAVE DIFFICULTY |
| BENDING OR STOOPING. SECTION |
| 11-4.1.3(10)(A). |
| 7. SUBMIT A DETAIL FOR THE BREAK ROOM |
| SINKS AND THE CONFERENCE ROOM SINK |
| SHOWING COMPLIANCE WITH 11-4.24 AND ALL |
| SUBSECTIONS. CLEAR FLOOR SPACE SHALL BE |
| FORWARD APPROACH AND EXTEND A MAXIMUM OF |
| 19" UNDERNEATH THE SINK. CABINET DOORS |
| SHALL NOT BE IN THE CLEAR FLOOR SPACE |
| FOR THE SINKS. REMOVE DOORS. |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. - |
| NO TRANSMITTAL LETTER WAS FOUND. |
| |