2005-07-15 00:00:00 | DENIED: 2ND REQUEST |
| REFERENCE PREVIOUS REVIEW DATED 4-6-05 |
| |
| COMMENT #1 A: PLEASE ANNOTATE ON PLANS |
| WHERE PENETRATIONS COMPLY WITH THE |
| CRITERIA LISTED IN 2001 FBC/M 607.1.3, |
| EXCEPTION #3 ITEMS 1 THROUGH 4. |
| |
| COMMENT #2:WALL TYPE 14 IS NOT |
| INDICATED ON PLAN SHEET A7.01, STORAGE |
| RM #214, ARCHITECTURAL PLAN INDICATE |
| EXISTING OPENING TO BE "PATCHED OR |
| CLOSED" IN WHICH THE "NEW" PART OF THE |
| WALL HAS A 1 HR RATING.PLEASE CLARIFY. |
| PLEASE NOTE, AIR IS TRANSFERRED FROM THE |
| STORAGE RM #214 BACK THE THE MECH |
| CLOSET, NO COMBUSTIBLES ARE TO BE STORED |
| IN THE |
| COMMENT #5: LIFE SAFTEY PLAN INDICATES 2 |
| HR RATING FOR THE "OPEN" AREA ON THE 4TH |
| FOR.SIDE WALL GRILLES DO NOT INDICATE |
| FIRE DAMPERS.PLEASE CLARIFY. |
| |
| COMMENT #6:PLAN SHEET C2 STILL |
| INDICATES A/C CONDENSATE INTO THE |
| SANITARY WHICH IS PROHIBITED BY THE CITY |
| CODE SEC. 90-125 (5). |
| |
| COMMENT #7:PLEASE CORRELATE THE LIFE |
| SAFETY & ARCHITRUAL PLANS. |
| ARCHITECTURAL PLANS INDICATE RATED WALLS |
| WEREAS THE THE LIFE SAFETY PLANS DO NOT |
| INDICATE RATING. |