Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2005-07-20 00:00:00******DENIED******
  
 IN ADDITION TO THE 1ST FIRE PLAN REVIEW
 COMMENTS THAT REQUIRE YOUR RESPONSE,
 PLEASE SEE THE FOLLOWING THAT WILL NEED
 TO BE ADDRESSED.
  
 1) ALL LIFE SAFETY TO COMPLY WITH NFPA
 101, 2003 EDITION, AND NFPA 1, 2003
 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 WILL BE REQUIRED FOR THE GENERATOR
 INSTALLATION AND FUEL SUPPLY.
  
 3) FIRE DEPARTMENT CONNECTION AND DOUBLE
 CHECK DETECTOR ASSEMBLY SHALL REMAIN
 UNOBSTRUCTED BY VEGETATION AND REMAIN
 ACCESSABLE.
  
 4) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDING HEIGHT REACHES 3 STORIES
 OR 30'.
  
 5) PLEASE EXPLAIN FIRE ACCESS LANE SHOWN
 ON SHEET A-0.02.
  
 6) PANIC HARDWARE IS REQUIRED ON DOORS
 SERVING AN ASSEMBLY AREA WITH OCCUPANT
 LOAD GREATER THAN 100 PERSONS.
  
 7) PLEASE ILLUSTRATE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS.
  
 8) 2A-10B,C FIRE EXTINGUISHERS SHALL VBE
 MOUNTED NOT TO EXCEED 75' TRAVEL
 DISTANCE.
  
 9) PLEASE NOTE THAT PENETRATIONS AND
 OPENINGS INTO EXIT ENCLOSURE ASSEMBLIES
 SHALL COMPLY WITH NFPA 101, SECTION
 7.1.3.2.1.
  
 10) SOME OF THE DOOR SWINGS APPEAR TO
 OBSTRUCT THE HALLWAYS BY GREATER THAN
 1/2 THE WIDTH OF THE EXIT ACCESS.
  
 11) DUCT SMOKE DETECTORS WHERE PROVIDED
 SHALL BE INSTALLED TO INITIATE A GENERAL
 FIRE ALARM WHEN ACTIVATED.
  
 12) ELEVATION DRAWINGS SHOW HANDRAILS IN
 THE MIDDLE OF THE ENTRANCE STAIRS. IN
 ADDITION, HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF STAIRS.
  
 13) PLEASE PROVIDE FLAME RETARDANT
 INFORMATION ON AWNINGS.
  
 14) AS PREVIOUSLY NOTED, NEW FIRE ALARM
 SYSTEMS SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 804-4756
  
  
  
  
  
  
  
  
  
  
  