Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop ENG
Sequence Number 2
Notes
Date Text
2005-07-05 00:00:00FAILED:
  
 1. SHEET C2, 2 OF 6 SHOWS THAT 3" PVC
 A / C COND. DRAIN CONNECTED TO THE
 SEWER, NOTE THAT THIS LINE COULD BE
 CONNECTED TO STORM WATER NOT TO THE
 SEWER.
 2. METERS MUST BE INSTALLED IN SIDEWALK'
 SEE CITY'S STANDARDS, WS-4 AND WS-6.
 3. DCDA AND BACKFOWS MUST BE LOCATED ON
 THE PROPERTY AND AT THE BACK OF THE
 SIDEWALK, THEY SHOULD BE HIDDEN FROM
 VIEW WITH SHRUBS.
 4 PLEASE VERIFY THE PROPOSED HANDICAP
 RAMP AS REGARD TO THE EXISTING SIDEWAK,
 IT SHOULD HAVE A 24" OF TRUNCATED DOME
 (DETECTABLE WARNING).
 5. NO LOCATION FOR DUMPSTER ENCLOSURE
 IS SHOWN, IS THERE ANY FOR THE SITE.
 6. PLEASE SUBMIT CIVIL PLANS ONLY TO
 THE PUBLIC UTILITIES AND ENGINEERING FOR
 THE APPROVAL ALL THE CONNECTIONS, ATT;
 MANNY GONZALEZ 494-1085.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI