Plan Review Notes For Permit 05030119 |
Permit Number |
05030119 |
|
Review Stop |
ENG |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-07-05 00:00:00 | FAILED: | | | | 1. SHEET C2, 2 OF 6 SHOWS THAT 3" PVC | | A / C COND. DRAIN CONNECTED TO THE | | SEWER, NOTE THAT THIS LINE COULD BE | | CONNECTED TO STORM WATER NOT TO THE | | SEWER. | | 2. METERS MUST BE INSTALLED IN SIDEWALK' | | SEE CITY'S STANDARDS, WS-4 AND WS-6. | | 3. DCDA AND BACKFOWS MUST BE LOCATED ON | | THE PROPERTY AND AT THE BACK OF THE | | SIDEWALK, THEY SHOULD BE HIDDEN FROM | | VIEW WITH SHRUBS. | | 4 PLEASE VERIFY THE PROPOSED HANDICAP | | RAMP AS REGARD TO THE EXISTING SIDEWAK, | | IT SHOULD HAVE A 24" OF TRUNCATED DOME | | (DETECTABLE WARNING). | | 5. NO LOCATION FOR DUMPSTER ENCLOSURE | | IS SHOWN, IS THERE ANY FOR THE SITE. | | 6. PLEASE SUBMIT CIVIL PLANS ONLY TO | | THE PUBLIC UTILITIES AND ENGINEERING FOR | | THE APPROVAL ALL THE CONNECTIONS, ATT; | | MANNY GONZALEZ 494-1085. | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | MOHAMMAD R. AMINI |
|