Date |
Text |
2005-07-11 00:00:00 | ************ UNSAT ************ |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| PLEASE ALSO SEE NEW NOTES. |
| |
| **************************************** |
| PLEASE SEE A RESPONSE LETTER WOULD HELP |
| IN THE REVIEW PROCESS IN ORDER TO |
| CLARIFY CERTAIN CODE ITEMS. |
| |
| **************************************** |
| |
| |
| 1)NOTE: PLEASE PROVIDE ALL LIGHT POLE/ |
| LIGHT FIXTURE WIND LOADING INFORMATION |
| FOR REVIEW AT THIS TIME. |
| PLEASE SEE MIN FBC 140 MPH. |
| IF "SITE LIGHTING" WIND LOAD INFORMATION |
| AND FIXTURE INFORMATION IS NOT PROVIDED |
| AT THIS TIME, A SEPARATE PERMIT MAY BE |
| APPLIED FOR AT A LATER DATE. |
| |
| 2)NOTE:PLEASE SEE FAC 61G15-23.002 FOR |
| MISSING INFORMATION REQUIRED ON TITLE |
| BLOCK FOR ENG FIRM. PLEASE ALSO SEE FS |
| 471.023. |
| PLEASE SEE THIS INFORMATION IS REQUIRED |
| ON ALL SHEETS AND FOR ALL TRADES |
| WHEATHER OR NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| |
| 3)NOTE:PLEASE SEE NOTES FOR ELECTRICAL |
| REFERENCES SOME CODES FROM THE 1996 NEC. |
| PLEASE SEE WE ARE CURRENTLY UNDER THE |
| 2002 NEC. |
| |
| 4)NOTE: PLEASE SEE 3.03, A "PANEL" IS |
| SHOWN BUT NO INDICATION OF WHAT PANEL |
| IS. |
| |
| 5)NOTE: PLEASE NOTE ON LIGHTNING |
| PROTECTION PLANS FOR ALL WORK TO BE |
| INSTALLED PER NFPA-780. |
| |
| 6)NOTE: PLEASE SUBMIT ALL INFORMATION ON |
| FIRE PUMP/ FIRE PUMP CONTROLLER. |
| PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| FOR BOTH. |
| PLEASE SEE NO SUBMITTIALS/SPECS/ CUT |
| SHEETS COULD BE LOCATED. |
| PLEASE SEE 230.76,230.79 FOR THE |
| REQUIRED MANUAL MEANS OF DISCONNECT |
| REQUIRED. PLEASE SPECIFY THIS ON PLANS. |
| PLEASE PLACE NOTE ONRISER DIAGRAM |
| THAT THE OVERCURRENT PROTECTIVE |
| DEVICE(S) SHALL BE SELECTED OR SET TO |
| CARRY INDEFINITELY THE SUM OF THE |
| LOCKED-ROTOR CURRENT OF THE FIRE PUMP |
| MOTOR(S) AND THE PRESSURE MAINTENANCE |
| PUMP MOTOR(S) AND THE FULL-LOAD CURRENT |
| OF THE ASSOCIATED FIRE PUMP ACCESSORY |
| EQUIPMENT WHEN CONNECTED TO THIS POWER |
| SUPPLY. |
| PLEASE SEE MISSING CONDUCTORS FROM FIRE |
| PUMP CONTROLLER TO FIRE PUMP. |
| PLEASE SEE FEEDER #9 SHOWS AN |
| EQUIPMENTGROUNDING CONDUCTOR FROM FPL TO |
| FIRST MEANS OF DISCONNECT. PLEASE SEE |
| 250.6,250.24, EQUIPMENT GROUNDS ARE ONLY |
| INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 7)NOTE: PELASE SEE 445.13 FOR SIZING OF |
| CONDUCTORS FROM GENERATOR.THE AMPACITY |
| OF THE CONDUCTORS FROM THE GENERATOR |
| TERMINALS TO THE FIRST DISTRIBUTION |
| DEVICE(S) CONTAINING OVERCURRENT |
| PROTECTION SHALL NOT BE LESS THAN 115 |
| PERCENT OF THE NAMEPLATE CURRENT RATING |
| OF THE GENERATOR. |
| |
| 8)NOTE: PLEASE SEE FEEDER #28 ON FEEDER |
| SCHEDULE, PLEASE CALRIFY # OF |
| CONDUCTORS? |
| |
| 9)NOTE: PLEASE INDICATE INFORMATION FOR |
| GENERATOR, GENERATOR SIZE ETC. |
| PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| FOR GEN/ ATS/ GEN SUB-BASE FUEL TANKS |
| ETC. |
| PLEASE SEE ATS FEED AND OCP IS SHOWN AS |
| 100A'S,, HOWEVER LOAD SHOWN EXCEEDS |
| RATING OF BRKR AND ATS. |
| PLEASE SHOW SIZING OF CONDUCTORS PER |
| ABOVE. |
| PLEASE SEE MISSING OCP AT GENERATOR>? |
| 215.5 |
| |
| 10)NOTE: PLEASE SEE 695.3, THE MAIN FOR |
| FIRE PUMP SHOULD NOT BE LOCATED IN THE |
| SAME ROOM AS NORMAL MAINS. PLEASE SEE IF |
| THERE WAS A FIRE OF SORTS IN MAIN |
| ELECTRICAL RM OR EQUIPMENT THIS WOULD |
| DIRECTLY AFFECT ELECTRICAL POWER TO FIRE |
| PUMP. |
| |
| 11)NOTE: PLEASE CORRELATE CIRCUTING FOR |
| RECEPTS IN ELEC/MACH/ELEV RMS WITH 1/4" |
| SCALE ON EACH SHEET WITH SAME RECEPTS |
| SHOWN ON PLANS. |
| 215.5 |
| |
| 12)NOTE: PLEASE SEE NOTE #1 ON E4.10 |
| ELECTRICAL NOTES MENTIONS, "MAIN CIRCUIT |
| BREAKERS IN PANEL BOARDS SHALL BE GROUND |
| FULAT PROTECTED" |
| PLEASE VERIFY THIS ? PLEASE SEE |
| 240.13,230.95 ETC WHEN GROUND FAULT |
| PROTECTION IS REQUIRED. THIS IS STILL IN |
| QUESTION. PLEASE EXPLAIN IN RESPONSE |
| LTR. |
| |
| 13)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| REQUESTED ON PREVIOUS REVIEW. |
| |
| 14)NOTE: PLEASE SHOW OR NOTE ALL TRACK |
| LIGHTING CALCULATIONS PER 220.12 |
| REQUESTED ON PREVISOU REVIEW. |
| |
| 15)NOTE: PLEASE SEE NOTE #22 ON E0.03 |
| FOR |
| |
| 16)NOTE: PLEASE SEE 700.16 AND 620.23A, |
| 620.24 FOR REQUIREMENTS IN ELEC RMS/ |
| ELEVATOR MACHINE RMS ETC. |
| PLEASE SEE THIS WAS REQUESTED ON |
| PREVIOUS REVIEW, HOWEVER NO CHANGES SEEM |
| TO HAVE BEEN MADE. A SEPARATE BRANCH |
| CIRCUIT SHALL SUPPLY THE MACHINE ROOM OR |
| CONTROL ROOM/MACHINERY SPACE OR CONTROL |
| SPACE LIGHTING AND RECEPTACLE(S). |
| |
| 17)NOTE: PLEASE PROVIDE ALTERNATING |
| CIRCUITING FOR ALL EGRESS AREAS. |
| ALTERNATING CIRCUITING IS ALREADY SHOWN |
| FOR STAIRWELLS.LS 101 7-9 |
| EMERGENCY LIGHTING SYSTEMS SHALL BE |
| DESIGNED AND INSTALLED SO THAT THE |
| FAILURE OF ANY INDIVIDUAL LIGHTING |
| CIRCUIT, SUCH AS THE BURNING OUT OF A |
| LIGHT BULB,TRIPPING OF A BREAKER OR |
| TURNING OFF OF A SWICTH CANNOT LEAVE IN |
| TOTAL DARKNESS ANY SPACE THAT REQUIRES |
| EMERGENCY ILLUMINATION. |
| WHERE HIGH-INTENSITY DISCHARGE LIGHTING |
| SUCH AS HIGH- AND LOW-PRESSURE SODIUM, |
| MERCURY VAPOR, AND METAL HALIDE IS USED |
| AS THE SOLE SOURCE OF NORMAL |
| ILLUMINATION, THE EMERGENCY LIGHTING |
| SYSTEM SHALL BE REQUIRED TO OPERATE |
| UNTIL NORMAL ILLUMINATION HAS BEEN |
| RESTORED. |
| |
| 18)NOTE: PLEASE SEE PLANS ARE INDICATING |
| BLDG AS "HISTORIC" YET IT IS UNCLEAR IF |
| BUILDING HAS "HISTORIC DESIGNATION"? |
| THIS IS ONLY NOTED: |
| |
| PLEASE SEE POSSIBLE NOTES FROM OTHER |
| REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SEE THERE MAY BE FURTHER COMMENTS |
| SINCE NOT ALL INFORMATION WAS SUBMITTED |
| FOR REVIEW. |
| |
| PLEASE REVMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STMAPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
2005-07-08 00:00:00 | IN ELEC FOR REVIEW. |