Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop E
Sequence Number 14
Notes
Date Text
2007-06-09 18:50:31** UNSAT **
 SHEETS E 2.02, 2.02C, 4.10 AND 5.01 HAVE COMMENTS. ALL
 OTHER SHEETS STAMPED AS REVIEWED.
  
 1) NOTE: PLEASE SEE PHOTO-METRICS ON WEST SIDE OF
 BUILDING DOES NOT INDICATE THE ENTIRE EGRESS PATH ON
 STAIRS FOR POINTS CALCULATED. THE AREA BY THE HAND
 RAILS IS ONLY PART OF THE STAIRS.
 PLEASE SEE LS 101 7.8.1.3, 7.9.2.
 PLEASE SEE THE CIRCUITING ON PLANS INDICATES EM-1, YET
 EM-1 ON PANEL SCHEDULE DOES NOT COORDINATE WITH THIS.
 ALL THREE STAIRS ARE NOTED WITH THE SAME EM-1.
 PLEASE REVISE E2.02, 2.02C.
  
 2) NOTE: PLEASE SEE RISER WHICH INDICATES MDH AS
 900AMPS WHICH THE CONDUCTORS AS SHOWN ON SCHEDULE WOULD
 NOT MEET 240.4C
 PLEASE SEE SHEET 5.01 AS THIS SHOWS AN 800AMP BUS AND A
 700AMP MAIN?
 PLEASE BE SURE TO COORDINATE THIS MAIN AND ANY OTHERS
 BEFORE SUBMITTING REVISIONS.
  
 3) NOTE: AS NOTED, PLEASE SEE THE GROUNDING DETAIL ON
 5.10 WHICH INDICATES *FENCE STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AT CHILLER PLANT. THIS SEEMS
 TO BE A MISPRINT. THIS WAS CONFIRMED WITH GC
 SUPERINTENDENT THAT THIS IS THE FOOTER STEEL. THIS WAS
 REDLINED ON THIS SHEET AND STAMPED.
  
  
 **OTHER PLAN SHEETS SUBMITTED STAMPED.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717