Plan Review Notes For Permit 05030119 |
Permit Number |
05030119 |
|
Review Stop |
E |
Sequence Number |
12 |
|
Notes |
Date |
Text |
2007-01-31 16:22:20 | *** UNSAT *** | | | | | | ** PLEASE SEE THE REVIEW NOTES DATED 12/27/06 | | | | 1) NOTE: PLEASE THE LIGHTING TO THE PUBLIC RIGHT OF WAY | | HAS NOT YET BEEN PROVIDED TO MEET NFPA-101 7.8.1.3, | | 7.9.2.2 | | | | 2) NOTE: PLEASE SEE THE SECOND SERVICE AS SHOWN AT THE | | CHILLER PLANT LOCATION IS NOT GRANTED AND THIS HAS ALSO | | BEEN CONFIRMED WITH THE CHIEF ELECTRICAL INSPECTOR. | | PLEASE SEE THE PLANS DO NOT PROVIDE THE INFORMATION OR | | DESIGN TO MEET 230.2 AND FOR THE AHJ TO GRANT SPECIAL | | PERMISSION. | | | | 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF | | WORK HAS NOT BEEN ADJUSTED FOR ACTUAL WORK. THIS MUST | | BE DONE. | | PLEASE SEE106.5 UNDER THE 2001 FBC AND 108.3 UNDER THE | | 2004 FBC BOTH ADMIN SECTIONS. | | | | 4) NOTE: PLEASE KNOW AS THE SERVICE RISER SHOWN IS NOT | | GRANTED OR PERMITTED, REVIEW FOR OTHER ITEMS FOR CODES | | COMPLIANCE IS NOT BEING DONE AT THIS TIME. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|