Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY CODE W.P.B.
  
 1) ALL SHEETS SHALL BE SIGNED, SEALED, &
 DATED. ALL SHEETS SHALL CONTAIN A TITLE
 BLOCK WITH ALL REQUIRED INFORMATION AND
 LICENCES. FAC 61G1-16.004 -
 61G14-23.002(2) AND FS 481.219 -
 481.2055 - 471.025.
 2) SHT C2 CONDENSATE WATER SHALL NOT
 DRAIN INTO THE SANITARY SEWER SYSTEM.
 THE CONDENSATE SHALL DRAIN SEPARATELY
 OUT OF THE BUILDING AND SHALL CONNECT TO
 A STORM LINE, CATCH BASIN, OR DRYWELL.
 CITY CODE 90-125(B)(5). A RELIEF VENT IS
 REQUIRED ON CONDENSATE LINE AS IT EXITS
 THE BUILDING.
 3) SHT A-1.05 SECONDARY ROOF DRAINS FOR
 THE EAST SIDE OF THE BUILDING ARE NOT
 SHOWN. PLEASE INDICATE THE LOCATION AND
 SIZE. SECTION 1107.
 4) SHT A-1.06 SCUPPER DETAIL (2) PLEASE
 INDICATE WIDTH AND HEIGHT DIMENSIONS TO
 DETERMINE AREA. SECTIONS 1107 & 104.2.1.
 5) SHT A-6.09 THE FOLLOWING INFORMATION
 IS MISSING FROM THE ACCESSIBILITY
 REQUIREMENTS. SHOW: CLEAR FLOOR SPACE
 FOR THE URINAL 11-4.18.3. - CLEAR FLOOR
 SPACE FOR THE LAV OUTSIDE THE STALL FOR
 PERSONS USING THE ACCESSIBLE URINAL
 11-4.19.3. - EXPOSED PIPES AND SURFACES
 11-4.19.4. - ALL ACCESSIBLE W/C'S SHALL
 BE 18" FROM CENTERLINE OF FIXTURE TO THE
 WALL. SEE FIG. 29.
 6) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH 11-4.15.2 SPOUT HEIGHT, 11-4.15.3
 SPOUT LOCATION, 11-4.15.4 CONTROLS, AND
 11-4.15.5 CLEARANCES/CLEAR FLOOR SPACE.
 ALSO FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING SECTION
 11-4.1.3(10)(A).
 7) SUBMIT A DETAIL FOR THE BREAK ROOM
 SINKS AND THE CONFERENCE ROOM SINK
 SHOWING COMPLIANCE WITH 11-4.24 AND ALL
 SUBSECTIONS. CLEAR FLOOR SPACE SHALL BE
 FORWARD APPROACH AND EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK. CABINET DOORS
 SHALL NOT BE IN THE CLEAR FLOOR SPACE
 FOR THE SINKS. REMOVE DOORS
 8) SHT A-6.10 DERTAILS 2, & 3. W/C'S TO
 BE 18" OFF WALL TO CENTERLINE OF THE
 FIXTURE. FIG. 29.
 9)SHT A-9.06 DETAIL #10 29" KNEE
 CLEARANCE REQUIRED. DETAIL SHOWS 26".
 10) SHT P-2.01 CENTER RWL'S (2) FOR EAST
 SIDE OF ROOF MISSING. SHOW LOCATION FOR
 BOTH. SECTION 104.2.1.
 11) SHT P-2.02 NO SANT. SHOWN TO THE W/C
 IN THE ACCESSIBLE STALL IN THE WOMEN'S
 TOILET ROOM. SECTION 104.2.1.
 12) SUBMIT RISER DIAGRAMS FOR THE
 SANITARY, THE STORM, WATER, &
 CONDENSATE. SECTION 104.2.1.
 13) SUBMIT BUILDING DRAIN ISOMETRICS FOR
 THE SANITARY, (SHOWING DFU'S AS THEY
 ACCUMULATE), THE STORM, (SHOWING SQUARE
 FOOTAGE AS IT ACCUMULATES), AND
 CONDENSATE. SHOW ALL PIPE SIZES.
 14) SUBMIT A WATER ISOMETRIC SHOWING ALL
 PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTORS LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" PER PDI-WH 201.
 15) SHT P-5.02 SUBMIT MANUFACTURE
 SPECIFICATION SHEETS FOR DOMESTIC
 BOOSTER PUMP SHOWING LISTING.
 16) SINCE ARCHITECTURAL PLANS ARE 75%
 FINISHED, AND PLUMBING PLANS ARE 50%
 FINISHED, MORE NEW COMMENTS MAY FOLLOW
 NEXT REVIEW.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  