Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop M
Sequence Number 1
Notes
Date Text
2005-04-06 00:00:00DENIED:
 1.PLAN SHEET M-2.01 - FIRE DAMPERS ARE
 NOT INDICATED AT THE FOLLOWING
 LOCATIONS; ROOM #108, 134, 113, 122 AND
 VARIOUS PENETRATIONS INTO THE CORRIDOR.
 PLEASE NOTE THE FOLLOWING:
 A) SOME DUCT PENETRATIONS INTO THE
 CORRIDOR MAY NOT REQUIRE FIRE
 FIRE DAMPERS BUT MUST COMPY WITH
 2001 FBC/M 607.1.3, EXCEPTION #3
 ITEMS 1 THROUGH 4.
 B) 2001 FBC 1006.1.3, PENETRATIONS INTO
  
 & OPENINGS THROUGH A STAIRWAY
 ENCLOSURE ARE PROHIBITED.
 C) SPECIFIC LOCATION OF EACH FIRE
 DAMPER SHALL BE IDENTIFIED ON THE
 PLAN PER 2001 FBC/M 607.6.
  
 2.PLAN SHEET M-2.02 - FIRE DAMPERS NOT
 INDICATED AT THE FOLLOWING LOCATIONS;
 CORRIDORS AT THE FOYER, ROOM #227, 212,
 AT THE STAIRWAY ENCLOSURE AND ROOM 221.
  
 3.PLAN SHEET M-2.02 - MECHANICAL ROOMS
 INDICATE OUTSIDE AIR INTO THE MECH ROOM
 BUT NOT TAPPED INTO THE RETURN AIR.
 SHOULD THIS MECH ROOM BE A PLENUM, IT
 SHALL COMPLY WITH 2001 FBC/M 603.9.NO
 COMBUSTIBLES ALLOWED IN THE RETURN AIR
 PLENUM.
  
 4.PLAN SHEET M-2.03 - FIRE DAMPERS NOT
 INDICATED AT THE FOLLOWING LOCATIONS;
 ROOMS 308 & 311 AND THE CORRIDOR.
 PENETRATIONS ARE ALSO INDICATED AT THE
 NORTH, SOUTH AND WEST STARIWAYS.
  
 5.PLAN SHEET M-2.04 - FIRE DAMPERS NOT
 INDICATED AT THE SIDE WALL GRILLES
 TERMINATING AT THE RATED WALL.
  
 6.PLAN SHEET C2 INDICATES A/C
 CONDENSATE TO THE SEWER WHICH IS
 PROHIBITED BY THE CITY CODE SEC. 90-125
 (5).
  
 7.PLEASE NOTE THE LIFE SAFETY PLAN AND
 ARCHITECTURAL PLANS CONFLICT.THE
 ARCHITECTURAL PLANS INDICATE ALL
 MECHANICAL ROOM AS HAVING A 1 HR FIRE
 RATING & THE LIFE SAFETY PLAN DOES NOT
 REFLECT THIS.PER THE 2001 FBC 503 THE
 1HR RATING FOR THE MECHANICAL ROOM IS
 NOT REQUIRED.PLEASE CLARIFY AND
 CORRELATE THE PLANS.IF THE RATING
 SHOULD REMAIN, FIRE DAMEPRS WILL BE
 REQUIRED AT THE PENETATRATIONS.
  
 8.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC/M TABLE 403.3.
  
 9.PLAN SHEETS A-1.02, A-1.03, A-1.04
 INDICATE "MECH SHAFT", PLEASE PROVIDE
 DETAIL OF THE SHAFT AND PENTRATIONS INTO
 THE SHAFT.
  
 10. PROVIDE INFORMATION AND SUBMITTAL
 FOR THE GENERATOR.INDICATE TYPE OF
 FUEL (NATURAL GAS, FUEL, DIESEL).
  
 11. IDENTIFY EXHAUST DUCT AND
 TERMINATION OF EXHAUST.
  
 12. SHOW COMPLIANCE WITH THE ENERGY CODE
 PER 2001 FBC CHAPTER 13 SECTION 103.0.
  
 PLEASE NOTE, PLANS ARE TO SIGNED,
 SEALED, AND DATED BY THE
 ENGINEER/ARCHITECT PER FS471.025 &
 481.221.PLEASE PROVIDE PRINTED NAME
 ADDRESS AND PHONE NUMBER OR TITLE BLOCK
 AS REQUIRED BY FAC61G15-23.002 &
 61G1-16.004.IF PRACTICING UNDER A DULY
 AUTHORIZED ENGINEERING BUSINESS, PROVIDE
 CERTIFICATE OF AUTHORIZATION # ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  