2005-04-06 00:00:00 | DENIED: |
| 1.PLAN SHEET M-2.01 - FIRE DAMPERS ARE |
| NOT INDICATED AT THE FOLLOWING |
| LOCATIONS; ROOM #108, 134, 113, 122 AND |
| VARIOUS PENETRATIONS INTO THE CORRIDOR. |
| PLEASE NOTE THE FOLLOWING: |
| A) SOME DUCT PENETRATIONS INTO THE |
| CORRIDOR MAY NOT REQUIRE FIRE |
| FIRE DAMPERS BUT MUST COMPY WITH |
| 2001 FBC/M 607.1.3, EXCEPTION #3 |
| ITEMS 1 THROUGH 4. |
| B) 2001 FBC 1006.1.3, PENETRATIONS INTO |
| |
| & OPENINGS THROUGH A STAIRWAY |
| ENCLOSURE ARE PROHIBITED. |
| C) SPECIFIC LOCATION OF EACH FIRE |
| DAMPER SHALL BE IDENTIFIED ON THE |
| PLAN PER 2001 FBC/M 607.6. |
| |
| 2.PLAN SHEET M-2.02 - FIRE DAMPERS NOT |
| INDICATED AT THE FOLLOWING LOCATIONS; |
| CORRIDORS AT THE FOYER, ROOM #227, 212, |
| AT THE STAIRWAY ENCLOSURE AND ROOM 221. |
| |
| 3.PLAN SHEET M-2.02 - MECHANICAL ROOMS |
| INDICATE OUTSIDE AIR INTO THE MECH ROOM |
| BUT NOT TAPPED INTO THE RETURN AIR. |
| SHOULD THIS MECH ROOM BE A PLENUM, IT |
| SHALL COMPLY WITH 2001 FBC/M 603.9.NO |
| COMBUSTIBLES ALLOWED IN THE RETURN AIR |
| PLENUM. |
| |
| 4.PLAN SHEET M-2.03 - FIRE DAMPERS NOT |
| INDICATED AT THE FOLLOWING LOCATIONS; |
| ROOMS 308 & 311 AND THE CORRIDOR. |
| PENETRATIONS ARE ALSO INDICATED AT THE |
| NORTH, SOUTH AND WEST STARIWAYS. |
| |
| 5.PLAN SHEET M-2.04 - FIRE DAMPERS NOT |
| INDICATED AT THE SIDE WALL GRILLES |
| TERMINATING AT THE RATED WALL. |
| |
| 6.PLAN SHEET C2 INDICATES A/C |
| CONDENSATE TO THE SEWER WHICH IS |
| PROHIBITED BY THE CITY CODE SEC. 90-125 |
| (5). |
| |
| 7.PLEASE NOTE THE LIFE SAFETY PLAN AND |
| ARCHITECTURAL PLANS CONFLICT.THE |
| ARCHITECTURAL PLANS INDICATE ALL |
| MECHANICAL ROOM AS HAVING A 1 HR FIRE |
| RATING & THE LIFE SAFETY PLAN DOES NOT |
| REFLECT THIS.PER THE 2001 FBC 503 THE |
| 1HR RATING FOR THE MECHANICAL ROOM IS |
| NOT REQUIRED.PLEASE CLARIFY AND |
| CORRELATE THE PLANS.IF THE RATING |
| SHOULD REMAIN, FIRE DAMEPRS WILL BE |
| REQUIRED AT THE PENETATRATIONS. |
| |
| 8.PROVIDE OUTSIDE AIR CALCULATIONS IN |
| ACCORDANCE WITH 2001 FBC/M TABLE 403.3. |
| |
| 9.PLAN SHEETS A-1.02, A-1.03, A-1.04 |
| INDICATE "MECH SHAFT", PLEASE PROVIDE |
| DETAIL OF THE SHAFT AND PENTRATIONS INTO |
| THE SHAFT. |
| |
| 10. PROVIDE INFORMATION AND SUBMITTAL |
| FOR THE GENERATOR.INDICATE TYPE OF |
| FUEL (NATURAL GAS, FUEL, DIESEL). |
| |
| 11. IDENTIFY EXHAUST DUCT AND |
| TERMINATION OF EXHAUST. |
| |
| 12. SHOW COMPLIANCE WITH THE ENERGY CODE |
| PER 2001 FBC CHAPTER 13 SECTION 103.0. |
| |
| PLEASE NOTE, PLANS ARE TO SIGNED, |
| SEALED, AND DATED BY THE |
| ENGINEER/ARCHITECT PER FS471.025 & |
| 481.221.PLEASE PROVIDE PRINTED NAME |
| ADDRESS AND PHONE NUMBER OR TITLE BLOCK |
| AS REQUIRED BY FAC61G15-23.002 & |
| 61G1-16.004.IF PRACTICING UNDER A DULY |
| AUTHORIZED ENGINEERING BUSINESS, PROVIDE |
| CERTIFICATE OF AUTHORIZATION # ON PLANS. |
| |