Date |
Text |
2005-03-10 00:00:00 | 1. PLEASE PROVIDE DOCUMENTATION FROM |
| NATIONAL, STATE OR THE LOCAL LEVEL |
| VERIFYING THE HISTORIC BUILDING |
| DESIGNATION. |
| |
| 2. CONSTRUCTION, DEMOLITION, AND |
| RENOVATION TO COMPLY WITH NFPA 241. |
| |
| 3. EXIT STAIRS ARE TO BE KEPT UP |
| WITH CONSTRUCTION. |
| |
| 4. DEBRIS SHALL BE REMOVED FROM THE |
| SITE DAILY. |
| |
| 5. NO CUTTING OR WELDING OPERATIONS |
| SHALL BE PERFORMED UNLESS APPROVED |
| BY THE FIRE PREVENTION BUREAU AND |
| FULL COMPLIANCE WITH NFPA 51B. |
| |
| 6. ELECTRONIC SWITCHES, CHAIN AND |
| LOCKS ARE REQUIRED ON THE BACKFLOW |
| DEVICE. |
| |
| 7. THE FIRE DEPARTMENT CONNECTION |
| SHALL BE INSTALLED ON THE PROPER |
| SIDE OF THE BACKFLOW DEVICE. |
| |
| 8. A KNOX-BOX WILL BE REQUIRED FOR |
| THE PROJECT. |
| |
| 9. HANDRAILS ARE REQUIRED ON BOTH |
| SIDES OF NEW STAIRS. |
| |
| 10. THE FIRE DEPARTMENT CONNECTION |
| SHALL BE LOCATED NO FARTHER THAN |
| 150 FEET FROM A FIRE HYDRANT. |
| |
| 11. THE USE OF GASOLINE POWERED |
| EQUIPMENT INDOORS MUST BE PROVIDED |
| WITH ADEQUATE VENTILATION TO PREVENT |
| THE BUILD-UP OF CARBON MONOXIDE. |
| |
| 12. THE BUILDING ADDRESS IS REQUIRED |
| ON THE PROPER ELEVATION. A MINIMUM OF |
| AT LEAST 6" HIGH NUMBERS ARE REQUIRED. |
| |
| 13. MORE DETAILS REQUIRED FOR EMERGENCY |
| GENERATOR AND FUEL SUPPLY. |
| |
| 14. SINCE THE BUILDING WILL BE |
| CONSIDERED A MIXED OCCUPANCY, THE |
| MOST STRINGENT OF THE TWO OCCUPANCY |
| TYPES SHALL GOVERN FOR DESIGN. |
| |
| 15. THE LIFE SAFETY PLAN SHALL INDICATE |
| THAT A COMPLETE AUTOMATIC FIRE |
| SPRINKLER SYSTEM WILL BE INSTALLED |
| THROUGHOUT THE BUILDING. |
| |
| 16. PLEASE INDICATE TENANT TYPE |
| ARRANGEMENTS FOR THE BUILDING. WILL |
| THE TENANT ARRANGEMENTS FOR THE |
| BUSINESS PORTION BE A SINGLE OR |
| MULTIPLE TENANT ARRANGEMENT. |
| |
| 17. PLEASE EXPLAIN NOTE "EXHIBIT SPACE |
| ONLY NOT TO BE OCCUPIED". |
| |
| 18. A MECHANICAL SHAFT APPEARS TO BE |
| LOCATED IN SOUTH STAIR 423 ON PAGE |
| A-0.13. ONLY CERTAIN ITEMS ARE |
| PERMITTED WITHIN STAIR ENCLOSURES |
| AND THIS IN NOT ONE OF THEM. |
| |
| 19. ELEVATOR WARNING SIGNS ARE REQUIRED. |
| |
| 20. EXTERIOR STAIRS SHALL BE SLIP |
| RESISTANT. |
| |
| 21. PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATIONS FOR WALLS AND |
| CEILINGS. |
| |
| 22. ALL SHAFTS THAT ARE LARGE ENOUGH |
| FOR PERSONS TO FALL INTO MUST BE |
| MARKED SHAFTWAY WITH 6" HIGH LETTERS. |
| |
| 23. ANY STORAGE AREAS LOCATED BENEATH |
| EXIT STAIRS SHALL BE RATED THE SAME |
| AS THE STAIRS. |
| |
| 24. PLEASE PROVIDE PRESCRIPTIVE |
| STRENGTH REQUIREMENTS FOR ALL |
| HANDRAILS AND GUARDRAILS. |
| |
| 25. PLEASE ILLUSTRATE ON THE ELEVATION |
| DRAWINGS THE LOCATIONS OF ANY OPERABLE |
| WINDOWS. |
| |
| 26. PLEASE EXPLAIN 10" TREADS. |
| |
| 27. PLEASE PROVIDE DETAILS ON SEALING |
| THE EXISTING GLASS TRANSOMES LOCATED |
| IN THE EXIT CORRIDORS. |
| |
| 28. THE WORD "HISTORIC" APPEARS IN |
| SEVERAL LOCALES ON THE PLANS. PLEASE |
| PROVIDE MORE DETAILS. |
| |
| 29. FIRE SPRINKLER HEADS SHALL NOT |
| BE IMPEDED BY THE INSTALLATION OF |
| ANY SOFFITS. |
| |
| 30. NO FIRE SPRINKLER DRAWINGS |
| PROVIDED WITH PLANS. |
| |
| 31. THE REQUIRED FIRE ALARM SYSTEM |
| SHALL BE MONITORED BY A UL LISTED |
| CENTRAL STATION APPROVED FOR CENTRAL |
| STATION SERVICE. |
| |
| 32. THE FIRE ALARM SYSTEM SHALL MONITOR |
| FIRE PUMP RUN, PUMP FAIL, AND PHASE |
| REVERSAL. |
| |
| 33. SEPARATE PLANS AND PERMITS REQUIRED |
| FOR FIRE ALARM AND FIRE SPRINKLER |
| SYSTEM. |
| |
| 34. NO COMBUSTIBLES ALLOWED IN THE |
| RETURN AIR PLENUM. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |