Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-03-10 00:00:001. PLEASE PROVIDE DOCUMENTATION FROM
 NATIONAL, STATE OR THE LOCAL LEVEL
 VERIFYING THE HISTORIC BUILDING
 DESIGNATION.
  
 2. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 3. EXIT STAIRS ARE TO BE KEPT UP
 WITH CONSTRUCTION.
  
 4. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 5. NO CUTTING OR WELDING OPERATIONS
 SHALL BE PERFORMED UNLESS APPROVED
 BY THE FIRE PREVENTION BUREAU AND
 FULL COMPLIANCE WITH NFPA 51B.
  
 6. ELECTRONIC SWITCHES, CHAIN AND
 LOCKS ARE REQUIRED ON THE BACKFLOW
 DEVICE.
  
 7. THE FIRE DEPARTMENT CONNECTION
 SHALL BE INSTALLED ON THE PROPER
 SIDE OF THE BACKFLOW DEVICE.
  
 8. A KNOX-BOX WILL BE REQUIRED FOR
 THE PROJECT.
  
 9. HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF NEW STAIRS.
  
 10. THE FIRE DEPARTMENT CONNECTION
 SHALL BE LOCATED NO FARTHER THAN
 150 FEET FROM A FIRE HYDRANT.
  
 11. THE USE OF GASOLINE POWERED
 EQUIPMENT INDOORS MUST BE PROVIDED
 WITH ADEQUATE VENTILATION TO PREVENT
 THE BUILD-UP OF CARBON MONOXIDE.
  
 12. THE BUILDING ADDRESS IS REQUIRED
 ON THE PROPER ELEVATION. A MINIMUM OF
 AT LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 13. MORE DETAILS REQUIRED FOR EMERGENCY
 GENERATOR AND FUEL SUPPLY.
  
 14. SINCE THE BUILDING WILL BE
 CONSIDERED A MIXED OCCUPANCY, THE
 MOST STRINGENT OF THE TWO OCCUPANCY
 TYPES SHALL GOVERN FOR DESIGN.
  
 15. THE LIFE SAFETY PLAN SHALL INDICATE
 THAT A COMPLETE AUTOMATIC FIRE
 SPRINKLER SYSTEM WILL BE INSTALLED
 THROUGHOUT THE BUILDING.
  
 16. PLEASE INDICATE TENANT TYPE
 ARRANGEMENTS FOR THE BUILDING. WILL
 THE TENANT ARRANGEMENTS FOR THE
 BUSINESS PORTION BE A SINGLE OR
 MULTIPLE TENANT ARRANGEMENT.
  
 17. PLEASE EXPLAIN NOTE "EXHIBIT SPACE
 ONLY NOT TO BE OCCUPIED".
  
 18. A MECHANICAL SHAFT APPEARS TO BE
 LOCATED IN SOUTH STAIR 423 ON PAGE
 A-0.13. ONLY CERTAIN ITEMS ARE
 PERMITTED WITHIN STAIR ENCLOSURES
 AND THIS IN NOT ONE OF THEM.
  
 19. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 20. EXTERIOR STAIRS SHALL BE SLIP
 RESISTANT.
  
 21. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 22. ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY WITH 6" HIGH LETTERS.
  
 23. ANY STORAGE AREAS LOCATED BENEATH
 EXIT STAIRS SHALL BE RATED THE SAME
 AS THE STAIRS.
  
 24. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 25. PLEASE ILLUSTRATE ON THE ELEVATION
 DRAWINGS THE LOCATIONS OF ANY OPERABLE
 WINDOWS.
  
 26. PLEASE EXPLAIN 10" TREADS.
  
 27. PLEASE PROVIDE DETAILS ON SEALING
 THE EXISTING GLASS TRANSOMES LOCATED
 IN THE EXIT CORRIDORS.
  
 28. THE WORD "HISTORIC" APPEARS IN
 SEVERAL LOCALES ON THE PLANS. PLEASE
 PROVIDE MORE DETAILS.
  
 29. FIRE SPRINKLER HEADS SHALL NOT
 BE IMPEDED BY THE INSTALLATION OF
 ANY SOFFITS.
  
 30. NO FIRE SPRINKLER DRAWINGS
 PROVIDED WITH PLANS.
  
 31. THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE MONITORED BY A UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE.
  
 32. THE FIRE ALARM SYSTEM SHALL MONITOR
 FIRE PUMP RUN, PUMP FAIL, AND PHASE
 REVERSAL.
  
 33. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 SYSTEM.
  
 34. NO COMBUSTIBLES ALLOWED IN THE
 RETURN AIR PLENUM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL