Plan Review Notes For Permit 05030119 |
Permit Number |
05030119 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-04 00:00:00 | FAILED: | | | | 1. PLEASE SUBMIT STORM WATER CALCULATION | | FOR OUR REVIEW AND APPROVAL, DESIGN MUST | | INCLUDE WATER QUALITY SYS. FOR THE | | ENTIRE SITE. | | 2. METERS MUST BE INSTALLED IN SIDEWALK, | | SEE CITY'S STANDARDS, WS-4 AND WS-6. | | 3. DCDA AND BACKFLOWS MUST BE LOCATED ON | | PROPERTY AND BACK OF THE SIDEWALK, THEY | | SHOULD BE HIDDEN FROM VIEW WITH SHRUBS. | | 4. PLEASE VRIFY THE PROPOSED HANDICAP | | RAMP AS REGARD TO THE EXISTING | | SIDEWALK, AND IT SHOULD HAVE A 24" | | OF TRUNCATED DOME(DETECTABLE WARNING). | | 5. PLEASE STATE THAT, HOW THE GARBAGE | | WILL BE PICKED UP, SHOW THE LOCATION, | | AND DETAILS FOR THE ENCLOSURE IF ANY. | | 6 PLEASE NOTE THAT THE CIVIL PLANS MUST | | BE REVIEWED FOR ALL THE CONNECTIONS BY | | PUBLIC UTILITIES AND ENGINEERING, | | CONTACT MANNY GONZALEZ AT 494-1085. | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | MOHAMMAD R. AMINI |
|