Date |
Text |
2005-03-10 00:00:00 | ********** UNSAT *********** |
| |
| |
| *** PLAN REVIEW ONLY ******* |
| PLEASE NOTE, PLANS ARE ONLY IN FOR PLAN |
| REVIEW AT THIS TIME AND HAVE NOT BEEN |
| SUBMITTED FOR PERMIT. |
| |
| 1)NOTE: PLEASE SEE PLANS ARE NOT |
| COMPLETE AT THIS TIME FOR FULL REVIEW |
| FOR CODE COMPLIANCE. |
| |
| 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULES. |
| PLEASE ALSO SEE AREAS WHERE ELECTRICAL |
| DEVICES ARE INDICATED IN"LT GRAY" AND |
| HANDWRITTEN ON PLANS? |
| |
| 3)NOTE: PLEASE PROVIDE ALL LIGHT POLE/ |
| LIGHT FIXTURE WIND LOADING INFORMATION |
| FOR REVIEW AT THIS TIME. |
| PLEASE SEE MIN FBC 140 MPH. |
| IF "SITE LIGHTING" WIND LOAD INFORMATION |
| AND FIXTURE INFORMATION IS NOT PROVIDED |
| AT THIS TIME, A SEPARATE PERMIT MAY BE |
| APPLIED FOR AT A LATER DATE. |
| |
| 4)NOTE:PLEASE SEE FAC 61G15-23.002 FOR |
| MISSING INFORMATION REQUIRED ON TITLE |
| BLOCK FOR ENG FIRM. PLEASE ALSO SEE FS |
| 471.023. |
| PLEASE SEE THIS INFORMATION IS REQUIRED |
| ON ALL SHEETS AND FOR ALL TRADES |
| WHEATHER OR NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| ** PLEASE SEE WHEN PLANS ARE FINALLY |
| SUBMITTED FOR PERMIT, PLANS MUST BE |
| SIGNED, DATED AND SEALED BY ALL |
| ARCHITECTS AND ENGINEERS RESPONSIBLE FOR |
| DRAWINGS. |
| FAC 61G1-16.004,61G15-23.002, FS |
| 481.221, 471.023 |
| |
| 5)NOTE: DUE TO PLANS ONLY IN FOR PLAN |
| REVIEW AT THIS TIME, IF SUBMITTED AFTER |
| JULY 1ST, 2005 THE 2005 NEC WILL BE IN |
| AFFECT. PLEASE SEE NEW REQUIREMENTS FOR |
| 2005 NEC AND CODES REFERENCE CHANGES. |
| PLEASE SEE 110.26 FOR CLEARENCE |
| REQUIREMENTS WHICH WILL CHANGE FOR |
| EQUIPMENT 1200A'S OR GREATER. |
| |
| 6)NOTE: PLEASE SEE 3.03, A "PANEL" IS |
| SHOWN BUT NO INDICATION OF WHAT PANEL |
| IS. |
| PLEASE ALSO SEE NOTE FOR A PANEL LCP-3C, |
| WITH AN ARROW TO A BLANK AREA? |
| |
| 7)NOTE: PLEASE SEE ROOF POWER PLANS IS |
| SHOWN BLANK? |
| |
| 8)NOTE: PLEASE SUBMIT ALL INFORMATION ON |
| FIRE PUMP/ FIRE PUMP CONTROLLER. |
| PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| FOR BOTH. |
| PLEASE SEE 230.76,230.79 FOR THE |
| REQUIRED MANUAL MEANS OF DISCONNECT |
| REQUIRED. PLEASE SPECIFY THIS ON PLANS. |
| PLEASE PLACE NOTE ONRISER DIAGRAM |
| THAT THE OVERCURRENT PROTECTIVE |
| DEVICE(S) SHALL BE SELECTED OR SET TO |
| CARRY INDEFINITELY THE SUM OF THE |
| LOCKED-ROTOR CURRENT OF THE FIRE PUMP |
| MOTOR(S) AND THE PRESSURE MAINTENANCE |
| PUMP MOTOR(S) AND THE FULL-LOAD CURRENT |
| OF THE ASSOCIATED FIRE PUMP ACCESSORY |
| EQUIPMENT WHEN CONNECTED TO THIS POWER |
| SUPPLY. |
| |
| 9)NOTE: PLEASE INDICATE INFORMATION FOR |
| GENERATOR, GENERATOR SIZE ETC. |
| PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| FOR GEN/ ATS/ GEN SUB-BASE FUEL TANKS |
| ETC. |
| PLEASE SEE SIZING OF CONDUCTORS ETC. |
| 215.5 |
| |
| 10)NOTE: PLEASE PLACE PANEL |
| RATINGS/AMPERAGE ON RISER DIAGRAM FOR |
| COORDINATION OF FEEDERS INSTALLATION AND |
| REVIEW. |
| 215.5 |
| |
| 11)NOTE: PLEASE COMPLETE RISER DIAGRAM |
| WITH ALL NOTATIONS FOR FEEDER SIZES, TO |
| CORRELATE WITH THE FEEDER SCHEDULE AT |
| RIGHT. |
| PLEASE SEE SOME FEEDERS MISSING ON RISER |
| AND ON FEEDER SCHEDULE. |
| PLEASE SEE MISSING FEED TO PANEL "LB". |
| PLEASE SEE MISSING #9 AND #10 FOR |
| FEEDERS. |
| PLEASE SEE MISSING OCP FOR FIRE PUMP AT |
| GENERATOR. |
| PLEASE SEE MISSING FEEDERS FOR MDAH,MDH, |
| ETC. |
| |
| 12)NOTE: PLEASE SEE NOTE #1 ON E4.10 |
| ELECTRICAL NOTES MENTIONS, "MAIN CIRCUIT |
| BREAKERS IN PANEL BOARDS SHALL BE GROUND |
| FULAT PROTECTED" |
| PLEASE VERIFY THIS ? PLEASE SEE |
| 240.13,230.95 ETC WHEN GROUND FAULT |
| PROTECTION IS REQUIRED. |
| |
| 13)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 14)NOTE: PLEASE SHOW OR NOTE ALL TRACK |
| LIGHTING CALCULATIONS PER 220.12 |
| |
| 15)NOTE: PLEASE SEE 250.50 FOR MISSING |
| COLD WATER PIPE ON GROUNDING ELECTRODE |
| SYSTEM. |
| |
| 16)NOTE: PLEASE SEE 700.16 AND 620.23A |
| FOR REQUIREMENTS IN ELEC RMS/ ELEV |
| MACHINE RMS ETC. |
| |
| EMERGENCY ILLUMINATION SHALL INCLUDE ALL |
| REQUIRED MEANS OF EGRESS LIGHTING, |
| ILLUMINATED EXIT SIGNS, AND ALL OTHER |
| LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| REQUIRED ILLUMINATION. |
| EMERGENCY LIGHTING SYSTEMS SHALL BE |
| DESIGNED AND INSTALLED SO THAT THE |
| FAILURE OF ANY INDIVIDUAL LIGHTING |
| ELEMENT, SUCH AS THE BURNING OUT OF A |
| LIGHT BULB, CANNOT LEAVE IN TOTAL |
| DARKNESS ANY SPACE THAT REQUIRES |
| EMERGENCY ILLUMINATION. |
| WHERE HIGH-INTENSITY DISCHARGE LIGHTING |
| SUCH AS HIGH- AND LOW-PRESSURE SODIUM, |
| MERCURY VAPOR, AND METAL HALIDE IS USED |
| AS THE SOLE SOURCE OF NORMAL |
| ILLUMINATION, THE EMERGENCY LIGHTING |
| SYSTEM SHALL BE REQUIRED TO OPERATE |
| UNTIL NORMAL ILLUMINATION HAS BEEN |
| RESTORED. |
| A SEPARATE BRANCH CIRCUIT SHALL SUPPLY |
| THE MACHINE ROOM OR CONTROL |
| ROOM/MACHINERY SPACE OR CONTROL SPACE |
| LIGHTING AND RECEPTACLE(S). |
| |
| PLEASE SEE POSSIBLE NOTES FROM OTHER |
| REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SEE SOME OF THESE ITMES LISTED |
| ABOVE HAVE BEEN REDLINED ON PLANS FOR |
| AREAS OF NOTES. |
| |
| PLEASE SEE NOTE #1. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
2005-03-08 00:00:00 | ONE ROLL IN ELEC FOR REVIEW. |
| |
| PLANS ONLY 50%COMPLETE FORP, M, E |
| AND FP. |