Plan Review Notes
Plan Review Notes For Permit 05030119
Permit Number 05030119
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-10 00:00:00********** UNSAT ***********
  
  
 *** PLAN REVIEW ONLY *******
 PLEASE NOTE, PLANS ARE ONLY IN FOR PLAN
 REVIEW AT THIS TIME AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE SEE PLANS ARE NOT
 COMPLETE AT THIS TIME FOR FULL REVIEW
 FOR CODE COMPLIANCE.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE ALSO SEE AREAS WHERE ELECTRICAL
 DEVICES ARE INDICATED IN"LT GRAY" AND
 HANDWRITTEN ON PLANS?
  
 3)NOTE: PLEASE PROVIDE ALL LIGHT POLE/
 LIGHT FIXTURE WIND LOADING INFORMATION
 FOR REVIEW AT THIS TIME.
 PLEASE SEE MIN FBC 140 MPH.
 IF "SITE LIGHTING" WIND LOAD INFORMATION
 AND FIXTURE INFORMATION IS NOT PROVIDED
 AT THIS TIME, A SEPARATE PERMIT MAY BE
 APPLIED FOR AT A LATER DATE.
  
 4)NOTE:PLEASE SEE FAC 61G15-23.002 FOR
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCK FOR ENG FIRM. PLEASE ALSO SEE FS
 471.023.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 ON ALL SHEETS AND FOR ALL TRADES
 WHEATHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 ** PLEASE SEE WHEN PLANS ARE FINALLY
 SUBMITTED FOR PERMIT, PLANS MUST BE
 SIGNED, DATED AND SEALED BY ALL
 ARCHITECTS AND ENGINEERS RESPONSIBLE FOR
 DRAWINGS.
 FAC 61G1-16.004,61G15-23.002, FS
 481.221, 471.023
  
 5)NOTE: DUE TO PLANS ONLY IN FOR PLAN
 REVIEW AT THIS TIME, IF SUBMITTED AFTER
 JULY 1ST, 2005 THE 2005 NEC WILL BE IN
 AFFECT. PLEASE SEE NEW REQUIREMENTS FOR
 2005 NEC AND CODES REFERENCE CHANGES.
 PLEASE SEE 110.26 FOR CLEARENCE
 REQUIREMENTS WHICH WILL CHANGE FOR
 EQUIPMENT 1200A'S OR GREATER.
  
 6)NOTE: PLEASE SEE 3.03, A "PANEL" IS
 SHOWN BUT NO INDICATION OF WHAT PANEL
 IS.
 PLEASE ALSO SEE NOTE FOR A PANEL LCP-3C,
 WITH AN ARROW TO A BLANK AREA?
  
 7)NOTE: PLEASE SEE ROOF POWER PLANS IS
 SHOWN BLANK?
  
 8)NOTE: PLEASE SUBMIT ALL INFORMATION ON
 FIRE PUMP/ FIRE PUMP CONTROLLER.
 PLEASE SUBMIT MANUFACTURE SPEC SHEETS
 FOR BOTH.
 PLEASE SEE 230.76,230.79 FOR THE
 REQUIRED MANUAL MEANS OF DISCONNECT
 REQUIRED. PLEASE SPECIFY THIS ON PLANS.
 PLEASE PLACE NOTE ONRISER DIAGRAM
 THAT THE OVERCURRENT PROTECTIVE
 DEVICE(S) SHALL BE SELECTED OR SET TO
 CARRY INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR CURRENT OF THE FIRE PUMP
 MOTOR(S) AND THE PRESSURE MAINTENANCE
 PUMP MOTOR(S) AND THE FULL-LOAD CURRENT
 OF THE ASSOCIATED FIRE PUMP ACCESSORY
 EQUIPMENT WHEN CONNECTED TO THIS POWER
 SUPPLY.
  
 9)NOTE: PLEASE INDICATE INFORMATION FOR
 GENERATOR, GENERATOR SIZE ETC.
 PLEASE SUBMIT MANUFACTURE SPEC SHEETS
 FOR GEN/ ATS/ GEN SUB-BASE FUEL TANKS
 ETC.
 PLEASE SEE SIZING OF CONDUCTORS ETC.
 215.5
  
 10)NOTE: PLEASE PLACE PANEL
 RATINGS/AMPERAGE ON RISER DIAGRAM FOR
 COORDINATION OF FEEDERS INSTALLATION AND
 REVIEW.
 215.5
  
 11)NOTE: PLEASE COMPLETE RISER DIAGRAM
 WITH ALL NOTATIONS FOR FEEDER SIZES, TO
 CORRELATE WITH THE FEEDER SCHEDULE AT
 RIGHT.
 PLEASE SEE SOME FEEDERS MISSING ON RISER
 AND ON FEEDER SCHEDULE.
 PLEASE SEE MISSING FEED TO PANEL "LB".
 PLEASE SEE MISSING #9 AND #10 FOR
 FEEDERS.
 PLEASE SEE MISSING OCP FOR FIRE PUMP AT
 GENERATOR.
 PLEASE SEE MISSING FEEDERS FOR MDAH,MDH,
 ETC.
  
 12)NOTE: PLEASE SEE NOTE #1 ON E4.10
 ELECTRICAL NOTES MENTIONS, "MAIN CIRCUIT
 BREAKERS IN PANEL BOARDS SHALL BE GROUND
 FULAT PROTECTED"
 PLEASE VERIFY THIS ? PLEASE SEE
 240.13,230.95 ETC WHEN GROUND FAULT
 PROTECTION IS REQUIRED.
  
 13)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 14)NOTE: PLEASE SHOW OR NOTE ALL TRACK
 LIGHTING CALCULATIONS PER 220.12
  
 15)NOTE: PLEASE SEE 250.50 FOR MISSING
 COLD WATER PIPE ON GROUNDING ELECTRODE
 SYSTEM.
  
 16)NOTE: PLEASE SEE 700.16 AND 620.23A
 FOR REQUIREMENTS IN ELEC RMS/ ELEV
 MACHINE RMS ETC.
  
 EMERGENCY ILLUMINATION SHALL INCLUDE ALL
 REQUIRED MEANS OF EGRESS LIGHTING,
 ILLUMINATED EXIT SIGNS, AND ALL OTHER
 LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION.
 EMERGENCY LIGHTING SYSTEMS SHALL BE
 DESIGNED AND INSTALLED SO THAT THE
 FAILURE OF ANY INDIVIDUAL LIGHTING
 ELEMENT, SUCH AS THE BURNING OUT OF A
 LIGHT BULB, CANNOT LEAVE IN TOTAL
 DARKNESS ANY SPACE THAT REQUIRES
 EMERGENCY ILLUMINATION.
 WHERE HIGH-INTENSITY DISCHARGE LIGHTING
 SUCH AS HIGH- AND LOW-PRESSURE SODIUM,
 MERCURY VAPOR, AND METAL HALIDE IS USED
 AS THE SOLE SOURCE OF NORMAL
 ILLUMINATION, THE EMERGENCY LIGHTING
 SYSTEM SHALL BE REQUIRED TO OPERATE
 UNTIL NORMAL ILLUMINATION HAS BEEN
 RESTORED.
 A SEPARATE BRANCH CIRCUIT SHALL SUPPLY
 THE MACHINE ROOM OR CONTROL
 ROOM/MACHINERY SPACE OR CONTROL SPACE
 LIGHTING AND RECEPTACLE(S).
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SEE SOME OF THESE ITMES LISTED
 ABOVE HAVE BEEN REDLINED ON PLANS FOR
 AREAS OF NOTES.
  
 PLEASE SEE NOTE #1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
2005-03-08 00:00:00ONE ROLL IN ELEC FOR REVIEW.
  
 PLANS ONLY 50%COMPLETE FORP, M, E
 AND FP.