Plan Review Notes For Permit 05030116 |
Permit Number |
05030116 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-08 00:00:00 | DENIED: | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW: | | | | 1.INDICATE NATURAL GAS OR LP GAS. | | 2.ADDITIONAL PERMIT REQUIRED FOR GAS | | 3.LP GAS - PROVIDE TANK CAPACITY AND | | LOCATION. | | 4.SITE PLAN SUBMITTED INDICATES | | GENERATOR AGAINST THE HOUSE.PLEASE | | PROVIDE CLEARANCES.THE MANUFACTURER'S | | INSTALLATION INSTRUCTIONS RECOMMEDS 5 FT | | CLEARNANCE. | | 5.INDICATE DISTANCE FROM PROPERTY LINE | | AND WINDOWS, DOORS, AND FRESH AIR | | INTAKES. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|