Plan Review Notes
Plan Review Notes For Permit 05030079
Permit Number 05030079
Review Stop M
Sequence Number 1
Notes
Date Text
2005-03-09 00:00:00PROVIDE THE FOLLOWING INFORMATION:
 1.INDICATE IF THE HOOD IS NEW OR USED.
 2.INDICATE GREASE DUCT MATERIAL &
 GAUGE.
 3.INDICATE CLEARANCES TO COMBUSTIBLES.
 4.PROIVIDE FAN INFORMATION.PLEASE
 NOTE FAN AND DUCT DESIGN SHALL PROVIDE A
 MINIMUM OF 1,500 FPM & NOT GREATER THAN
 2,500 FPM.
 5.PROVIDE DISTANCES TO PROPERTY LINES.
 6.PROVIDE MANUFACTURER'S SUBMITTAL
 DATA FOR THE GRILLE.