Date Text
2005-03-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} TWO SETS OF PLANS ARE REQUIRED FOR
 REVIEW PER 104.2.1 FBC.
  
 2} PLANS CONTAINING ARCHITECTS TITLE
 BLOCK MUST BE SIGNED, SEALED AND DATED
 BY SAME PER 481 F.S.ANY PLAN SUBMITTED
 MUST CONTAIN THE PRINTED AND SIGNED NAME
 OF THE PERSON RESPONSIBLE PER 104.2.1
 FBC.
  
 3} THE DESCRIPTION INDICATES 3 CAMERA'S
 BEING INSTALLED BUT ONLY ONE LOCATION
 SHOWN ON THE PLAN THAT I COULD FIND.
 PLEASE INDICATE LOCATIONS.
  
 4} THE VALUE ON THE APPLICATION MUST
 REFLECT ALL MATERIAL AND LABOR INCLUDED
 FOR COMPLETION OF DESCRIBED JOB PER
 104.6.5 WEST PALM BEACH AMMENDMENTS TO
 FBC. PLEASE INCREASE VALUE ON
 APPLICATION TO CORRECT VALUE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  