Plan Review Notes
Plan Review Notes For Permit 05021334
Permit Number 05021334
Review Stop E
Sequence Number 7
Notes
Date Text
2005-09-19 00:00:00********* UNSAT *****************
  
  
  
 1)NOTE: PLEASE SEE AS PREVIOUSLY
 REQUESTED. PLEASE SUBMIT COMPLETE
 SIGNED, DATED AND SEALED WIND LOADING
 CALCULATIONS FOR NEW LT POLES AND
 FXTURES. PLEASE SEE NO LT FIXTURES
 INCLUDED IN CALCUALTIONS, AND
 INFORMATION SUBMITTED WAS NOT SIGNED ,
 DATED OR SEALED.
 FS 471.025, FAC 61G15-23.002
  
 ** PLEASE NOTE**
 WIND LOADING CALCS WILL BE REVIEWED BY
 STRUCTUAL REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
 WIND LOAD CALCS SENT TO SH.