Plan Review Notes
Plan Review Notes For Permit 05021334
Permit Number 05021334
Review Stop P
Sequence Number 2
Notes
Date Text
2005-05-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 THE COMMENT NUMBER WILL REMAIN THE SAME
 AS THE PREVIOUS REVIEW:
 3) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND
 ON SHEET. PLEASE CORRELATE NOTES WITH
 FLOOR PLAN. SECTION 104.2.1. - RESPONSE
 NOTED, BUT CHANGE TO BE MADE ON PLANS
 NOT ONLY ON COMMENT REPLY RESPONSE
 SHEET.
 5) SHT A2.3 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW LOCATION OF SECONDARY
 DRAINS FOR SOUTH PORTION. SHOW SIZE OF
 PRIMARY ROOF DRAINS AND SECONDARY ROOF
 DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS
 AND DOWNSPOUTS AND INDICATE AREA BEING
 DRAINED BY EACH GUTTER AND DOWNSPOUT.
 SHOW SQUARE FOOTAGE FOR EACH ROOF AREA
 AND SHOW 1/2 AREA OF VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO SF OF ROOF
 IN CALCULATIONS. SHOW SLOPE OF GUTTERS
 AND THE HIGH POINT ON EACH GUTTER. -
 RESPONSE NOTED, BUT PLANS INDICATE THAT
 THE GUTTERS AND DOWNSPOUTS SHALL BE
 REPLACED, AND SIZE OF EACH SHALL BE
 INDICATED AND CALCULATIONS SHALL BE
 GIVEN TO MAKE SURE SIZE OF GUTTERS AND
 DOWNSPOUTS IS CORRECT PER SECTIONS 1106
 AND 1107.
 8) SHT P1.1 PLUMBING NOTES: #13 AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. SECTION 604.9. #14 DIELECTRIC
 UNIONS ARE NOT APPROVED FOR DISTRIBUTION
 WATER. DIELECTRIC COUPLINGS ARE
 APPROVED. - RESPONSE NOTED AND ITS
 CORRECT THAT 604.9 DOES NOT PROHIBIT THE
 USE OF AIR CHAMBERS, THE CITY OF WEST
 PALM BEACH DOES NOT APPROVE OF AIR
 CHAMBERS UNLESS THEY HAVE A "BLEED OFF
 VALVE ON TOP OF THE AIR CHAMBER, A SHUT
 OFF VALVE AT THE BASE OF THE AIR CHAMBER
 AND A DRAIN VALVE TO DRAIN THE WATER
 FROM THE AIR CHAMBER TO RECHARGE THE AIR
 CHAMBER PER ATTACHED SHEET FROM PDI-WH
 201 REPORT. ALSO AN ACCESS PANEL FOR
 EACH SET OF AIR CHAMBERS WILL BE
 REQUIRED FOR ACCESS TO THE VALVES ON THE
 AIR CHAMBERS. PDI-WH 201. - COMMENT #14
 RESPONSE NOTED - DIELECTRIC UNIONS ARE
 NOT MADE FOR WATER DISTRIBUTION WATER,
 SO A DIELECTRIC COUPLING SHALL BE USED.
 11) SHT P3.1 WATER PIPING DIAGRAM, AIR
 CHAMBERS ON BREAK ROOM SINK ARE NOT
 APPROVED. SECTION 604.9 DELETE FROM
 DIAGRAM. - RESPONSE NOTED. SEE COMMENT
 #8 AND IF THE VALVES, (3 EACH AIR
 CHAMBER), AND ACCESS PANEL WILL BE USED
 THAN THE AIR CHAMBERS WILL BE ALLOWED.
 PDI-WH 201.
 13) ALL SHEETS SIGNED/SEALED/DATED BY AN
 ARCHITECT SHALL SHOW FIRM LICENSE NUMBER
 CERTIFICATE OF AUTHORIZATION. FAC
 61G1-16.004(2) AND FS 481.219. -
 RESPONSE NOTED, BUT THE CA OR BUSINESS
 NUMBER IS NOT SHOWN IN THE TITLE BLOCK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]