Date |
Text |
2005-05-02 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: |
| THE COMMENT NUMBER WILL REMAIN THE SAME |
| AS THE PREVIOUS REVIEW: |
| 3) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND |
| ON SHEET. PLEASE CORRELATE NOTES WITH |
| FLOOR PLAN. SECTION 104.2.1. - RESPONSE |
| NOTED, BUT CHANGE TO BE MADE ON PLANS |
| NOT ONLY ON COMMENT REPLY RESPONSE |
| SHEET. |
| 5) SHT A2.3 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SECTIONS 1106, & 1107 AND ALL |
| SUBSECTIONS. SHOW LOCATION OF SECONDARY |
| DRAINS FOR SOUTH PORTION. SHOW SIZE OF |
| PRIMARY ROOF DRAINS AND SECONDARY ROOF |
| DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS |
| AND DOWNSPOUTS AND INDICATE AREA BEING |
| DRAINED BY EACH GUTTER AND DOWNSPOUT. |
| SHOW SQUARE FOOTAGE FOR EACH ROOF AREA |
| AND SHOW 1/2 AREA OF VERTICAL WALLS |
| INCLUDING PARAPETS ADDED TO SF OF ROOF |
| IN CALCULATIONS. SHOW SLOPE OF GUTTERS |
| AND THE HIGH POINT ON EACH GUTTER. - |
| RESPONSE NOTED, BUT PLANS INDICATE THAT |
| THE GUTTERS AND DOWNSPOUTS SHALL BE |
| REPLACED, AND SIZE OF EACH SHALL BE |
| INDICATED AND CALCULATIONS SHALL BE |
| GIVEN TO MAKE SURE SIZE OF GUTTERS AND |
| DOWNSPOUTS IS CORRECT PER SECTIONS 1106 |
| AND 1107. |
| 8) SHT P1.1 PLUMBING NOTES: #13 AIR |
| CHAMBERS ARE NOT APPROVED. DELETE FROM |
| REFERENCE. SECTION 604.9. #14 DIELECTRIC |
| UNIONS ARE NOT APPROVED FOR DISTRIBUTION |
| WATER. DIELECTRIC COUPLINGS ARE |
| APPROVED. - RESPONSE NOTED AND ITS |
| CORRECT THAT 604.9 DOES NOT PROHIBIT THE |
| USE OF AIR CHAMBERS, THE CITY OF WEST |
| PALM BEACH DOES NOT APPROVE OF AIR |
| CHAMBERS UNLESS THEY HAVE A "BLEED OFF |
| VALVE ON TOP OF THE AIR CHAMBER, A SHUT |
| OFF VALVE AT THE BASE OF THE AIR CHAMBER |
| AND A DRAIN VALVE TO DRAIN THE WATER |
| FROM THE AIR CHAMBER TO RECHARGE THE AIR |
| CHAMBER PER ATTACHED SHEET FROM PDI-WH |
| 201 REPORT. ALSO AN ACCESS PANEL FOR |
| EACH SET OF AIR CHAMBERS WILL BE |
| REQUIRED FOR ACCESS TO THE VALVES ON THE |
| AIR CHAMBERS. PDI-WH 201. - COMMENT #14 |
| RESPONSE NOTED - DIELECTRIC UNIONS ARE |
| NOT MADE FOR WATER DISTRIBUTION WATER, |
| SO A DIELECTRIC COUPLING SHALL BE USED. |
| 11) SHT P3.1 WATER PIPING DIAGRAM, AIR |
| CHAMBERS ON BREAK ROOM SINK ARE NOT |
| APPROVED. SECTION 604.9 DELETE FROM |
| DIAGRAM. - RESPONSE NOTED. SEE COMMENT |
| #8 AND IF THE VALVES, (3 EACH AIR |
| CHAMBER), AND ACCESS PANEL WILL BE USED |
| THAN THE AIR CHAMBERS WILL BE ALLOWED. |
| PDI-WH 201. |
| 13) ALL SHEETS SIGNED/SEALED/DATED BY AN |
| ARCHITECT SHALL SHOW FIRM LICENSE NUMBER |
| CERTIFICATE OF AUTHORIZATION. FAC |
| 61G1-16.004(2) AND FS 481.219. - |
| RESPONSE NOTED, BUT THE CA OR BUSINESS |
| NUMBER IS NOT SHOWN IN THE TITLE BLOCK. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |