2005-04-20 00:00:00 | **** UNSAT 2ND REVIEW **** |
| |
| PLANS ONLY IN FOR "PLAN REVIEW" AND NOT |
| SUBMITTED FOR PERMIT. |
| |
| 1NOTE: NOTE #1, NO, PLEASE SEE SAME |
| ELECTRICAL SHEET WITH OUT ANY REFERENCE |
| TO FBC 140 MPH . PLEASE ALSO SEE WE |
| COULD NOT LOCATE WIND LOADING |
| CALCULATIONS. |
| |
| 2)NOTE: NOTE #2 OK. |
| |
| 3)NOTE: NOTE #3 OK. |
| |
| 4)NOTE:NOTE #4 OK. |
| |
| 5)NOTE: NOTE #5 NO, PLEASE SEE RISER |
| STILL SHOWS AN EQUIPMENT GROUNDING |
| CONDUCTOR INSTALLED BEFORE THE FIRST |
| MEANS OF DISCONNECT. 250.6,250.24. |
| |
| 6)NOTE: NOTE #6 OK. |
| OCP LOCATED AT PANEL. |
| |
| NEW NOTE: |
| 1)NOTE:PLEASE SEE ELECTRICAL REVIEW |
| PREVIOUS NOTES MENTIONS TO SEE OTHER ) |
| PERTAINING TO POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S). PLEASE SEE NOTE #5 |
| FROM PREVIOUS BLDG REVIEW WHICH |
| REFERENCE WAS GIVEN TO FAC 61G1-16.004 |
| AND FS 481.219 WITH INFORMATION REQUIRED |
| ON TITLE BLOCKS. |
| PLEASE SEE THIS IS REQUIRED ON ALL |
| SHEETS AND FOR ALL TRADES WHEATHER OR |
| NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| PLEASE SEE NONE OF THE TRADE SHEETS HAVE |
| HAD TITLE BLOCKS CORRECTED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |