Plan Review Notes
Plan Review Notes For Permit 05021334
Permit Number 05021334
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A0.1 SHEET INDEX SHOWS CAR WASH
 DRAWINGS. THESE DRAWINGS WERE NOT
 LOCATED. PLEASE CLARIFY. SECTION
 104.2.1.
 2) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND
 ON SHEET. PLEASE CORRELATE NOTES WITH
 FLOOR PLAN. SECTION 104.2.1.
 3) SHT A2.1 SHOW CLEAR FLOOR SPACE FOR
 ACCESSIBLE URINAL AND BREAK ROOM SINK.
 (FORWARD APPROACH FOR SINK REQUIRED,
 MAXIMUM 19" UNDERNEATH SINK) SECTIONS
 11-4.18.3 & 11-4.19.3.
 4) SHT A2.1 DRINKING FOUNTAIN REQUIRED
 PER TABLE 403.1.
 5) SHT A2.3 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW LOCATION OF SECONDARY
 DRAINS FOR SOUTH PORTION. SHOW SIZE OF
 PRIMARY ROOF DRAINS AND SECONDARY ROOF
 DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS
 AND DOWNSPOUTS AND INDICATE AREA BEING
 DRAINED BY EACH GUTTER AND DOWNSPOUT.
 SHOW SQUARE FOOTAGE FOR EACH ROOF AREA
 AND SHOW 1/2 AREA OF VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO SF OF ROOF
 IN CALCULATIONS. SHOW SLOPE OF GUTTERS
 AND THE HIGH SPOT ON EACH GUTTER.
 6) SHT A9.1 THE FOLLOWING INFORMATION TO
 BE SHOWN ON THE ACCESSABILITY DETAIL #12
 FLUSH CONTROLS 11-4.16.5 (W/C) AND
 11-4.18.4 (URINAL).
 7) SHT P1.1 PARTIAL PLUMBING SITE PLAN,
 BACKFLOW SHALL BE AT LEAST THE SAME SIZE
 AS THE LINE IN WHICH THEY ARE INSTALLED.
 TABLE 603.1 FOOTNOTE "D".
 8) SHT P1.1 PLUMBING NOTES: #13 AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. SECTION 604.9 - #14
 DIELECTRIC UNIONS ARE NOT APPROVED FOR
 DISTRIBUTION WATER. DIELECTRIC UNIONS
 APPROVED.
 9) SHT P1.1 KEY NOTES #11 IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED. SECTION 704.5.
 10) CONDENSATE DRAINING INTO THE GUTTER
 FOR THE ROOF STORM WATER SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER
 AREAS SO AS TO CAUSE A SUISANCE. PLEASE
 INDICATE IF THE DISCHARGE OF THE
 DOWNSPOUST WILL BE INTO AREAS THAT WILL
 PERCOLATE INTO THE GROUND. SECTION
 M307.2.1(3)
 11) SHT P3.1 WATER PIPING DIAGRAM, AIR
 CHAMBERS ON BREAK ROOM SINK ARE NOT
 APPROVED. SECTION 604.9. DELETE FROM
 DIAGRAM. - SHOW THE SHUT OFF VALVE FOR
 THE HOSE BIBB. SECTION 606.2(2) - FULL
 OPEN VALVE REQUIRED ON ALL WATER
 DOWN-FEED PIPE. SECTION 606.1(4).
 12) SHT P3.1 SUBMIT MANUF. SPECIFICATION
 SHEETS FOR INSTA-HOT WATER HEATER TO
 SHOW LISTING.
 13) ALL SHEETS SIGNED/SEALED/DATED BY AN
 ARCHITECT SHALL SHOW FIRM LICENSE NUMBER
 CERTIFICATE OF AUTHORIZATION & PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT.
 FAC 61G1-16.004(2)(6) & FS 481.219 FS
 481.2055.
 14) ALL SHEETS SIGNED/SEALED/DATED BY AN
 ENGINEER SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICION THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE
 OF AUTHROIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.2055 (PME
 SHEETS OK) SEE C-1 & C-2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]