Plan Review Notes
Plan Review Notes For Permit 05021224
Permit Number 05021224
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05021224
 ADD: 1300 S DIXIE HWY
 CONT:RAPP CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SEE ELECTRICAL COMMENTS AS ENGINEERS
 FULL SIGNATURE, 471.025.PLANS,
 SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE WORK TO BE ACCOMPLISHED
 UNDER THIS PERMIT " SECOND FLOOR
 GRAPHICS HALL" BUT SHEET A-4.1.1
 INDICATES WORK ON THE FIRST FLOOR BACK
 STAGE COORIDOR 126 AND STORAGE AREA, IS
 THERE WORK TO BE COMPLETED UNDER THIS
 PERMIT OR ELSEWHERE ON THE FIRST FLOOR?
  
 4) PLANS (A-321) INDICATE WORK IN
 HALLWAY # 204, SEE SECTION 1021.4 DOORS
 SWINGING INTO A CORRIDOR SHALL BE
 RECESSED TO PREVENT INTERFERENCE WITH
 CORRIDOR TRAFFIC OR SWING OPEN 180
 DEGREES. DOORS IN ANY POPSITION SHALL
 NOT REDUCE THE CORRIDOR WIDTH BY MORE
 THAN ONE HALF.
  
 5A) A-2.2.3 NOTE# 7 REFERS TO LIFE
 SAFETY PLAN FOR LOCATION AND DETAILS OF
 1-HR RATED CEILING ABOVE 2X2 ACT
 CEILING, CAN NOT FIND THE LIFE SAFETY
 PLAN REFRENCED.
 5B) DIRECTLY BELOW THIS NOTE IS A
 DESIGNATION FOR A 1 HR RATED WALL, WALL
 IS NOT SHOWN ON PLANS.
  
 6) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS DO NOT INDICATE THE MINIMUM BLDG
 TYPE OR IF 1HR PROTECTED OR FIRE
 SPRINKLERED?
  
 7)1005.4 EMERGENCY ESCAPE AND RESCUE
 OPENINGS, (2) EVERY ROOM OR SPACE
 GREATER THAN 250 FT USED FOR CLASSROOM
 OR OTHER ED- UCATIONAL PURPOSES OR
 NORMALLY SUBJECT TO STUDENT OCCUPANCY,
 AND EVERY ROOM SUBJECT TO CLIENT
 OCCUPNCY SHALL NOT HAVE NOT LESS THAN
 ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE,
 SEE EXCEPTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  