Plan Review Notes For Permit 05021123 |
Permit Number |
05021123 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-07 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE ENGINEERS TITLE BLOCK MUST BE | | SEALED AND HIS NAME SIGNED TO THE PLAN. | | IF NOT TAKING RESPONSIBILITY FOR THE | | PLAN, REMOVE ALL. THE PERSON TAKING | | RESPONSIBILITY MUST COMPLY WITH 104.2.1 | | FBC. AND ALL APPLICABLE STATUTES IF A | | DESIGN PROFESSIONAL. | | | | 2} PLEASE SUBMIT A RISER DIAGRAM THAT | | INDICATES ACTUAL CONDITIONS. THERE IS | | ONE SERVICE WITH TWO METERS SHOWN ON THE | | PLAN, AND TWO SEPERATE RISERS DEPICTED | | ON THE RISER. PLEASE CORRELATE. | | | | 3} THE RISER SHOULD ALSO INDICATE | | COMPLIANCE WITH WITH 250.32(GROUNDING) | | AT THE HOUSE. | | | | 4} PLEASE SEE RECEPTACLES NEED TO BE | | ADDED FOR 210.52(A)(1)&(2)THE GUEST | | BEDROOM AND THE KITCHENETTE. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|