Plan Review Notes For Permit 05021038 |
Permit Number |
05021038 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-18 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | | | 1} PLEASE SHOW THE PANEL LOCATION. | | | | 2} PLEASE CALCULATE THE FAULT CURRENT | | FOR THE SERVICE, INDICATE SAME AND GIVE | | AIC RATING FOR THE EQUIPMENT. | | | | 3} A SMOKE DETECTOR MUST BE LOCATED IN | | CLOSE PROXIMITY OF THE STAIRWELL PER | | 905.2.2 FBC. | | | | 4} THE KITCHEN COUNTERTOP SPACING MUST | | COMPLY WITH 210.52(C). | | | | 5} THE PERSON RESPONSIBLE FOR THE | | DRAWING MUST PRINT AND SIGN SAME PER | | 104.2.1 FBC, IF DESIGN PROFESSIONAL 471 | | OR 481 FS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|