Plan Review Notes
Plan Review Notes For Permit 05021038
Permit Number 05021038
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.) ADDITIONAL FEES DUE TO VALUE
 ADJUSTMENT.2192SF X 76.96, 525 X 41.6,
 TOTAL OF 190,536.SEE ATTACHED INVOICE.
  
 4.) NO EMERGENCY MEANS OF ESCAPE
 FBC1005.4.5 IS SHOWN ON THE PLAN.THE
 PRODUCT APPROVALS SUBMITTED FOR THE
 FRONT DOOR SHOW A GLAZED DOOR REQUIRING
 IMPACT PROTECTION.SHOW THE EMERGENCY
 MEANS OF ESCAPE ON THE PLAN AND SUBMIT
 COMPLIANT PRODUCT APPROVALS.
  
 5.)THE TEST REPORT FOR THE OVERHEAD
 DOOR HAS A DESIGN PRESSURE LIMITATION OF
 +46/-52.THIS IS NOT SHOWN ON THE STATE
 PRODUCT APPROVAL PROVIDED.CLEARLY
 INDICATE ON THE STATE PRODUCT APPROVAL
 WHICH PRODUCT YOU ARE INSTALLING.
  
 6.)CIRCLE THE .PDF FILE LINK ON THE
 STATE PRODUCT APPROVAL SUBMITTED FOR THE
 SLIDING GLASS DOOR.
  
 7.)IN ADDITION TO THE FRONT DOOR,
 OVERHEAD DOOR, SLIDING GLASS DOOR,
 REFERENCED ABOVE, PRODUCT APPROVALS
 (FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 WITH TEST REPORT AND INSTALLATION
 INSTRUCTIONS) REQUIRED FOR:
 ROOF TILE
 SINGLE HUNG WINDOW
 IMPACT PROTECTION WITH INSTALLATION
 SCHEDULE, SEE ATTACHED
 MULLIONS
  
 8.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC13-103.1.2.
  
 9.)SPECIFY DESIGN CRITERIA FOR
 HANDRAIL AND GUARDRAIL SHEET 1,
 FBC1608.2.1 AND 1608.2.2.NOTE THAT
 DESIGN CRITERIA IS DIFFERENT FOR RAILS
 WHICH SERVE AS A GUARDRAIL.ALSO SEE
 FBC1026.5.1.
  
 10.) PROVIDE STRUCTURAL DETAIL FOR THE
 STAIRS, INCLUDING FIREBLOCKING.
  
 11.) REMOVE OR CROSS OFF DETAILS ON D1
 WHICH DO NOT APPLY TO THIS JOB.
  
 12.) PROVIDE WIND DESIGN INFORMATION ON
 THE PLAN FBC1606.1.7.
  
 13.) TYPICAL WALL SECTION, SHEET 6,
 SHOWS 8 INCH RECESS FOR BLOCK.REVISE.
  
 14.) PROVIDE A DRAFTSTOP DETAIL AND
 SCHEDULE (ON THE FLOOR FRAMING PLAN),
 FBC705.3.
  
 15.) STRUCTURAL NOTES D1, 1, ROOF
 NAILING SPECIFIED NOT COMPLIANT FOR ZONE
 3, FBC*TABLE 2306.1.
  
  