Plan Review Notes
Plan Review Notes For Permit 05021036
Permit Number 05021036
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-18 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} COMPLETE THE RISER DIAGRAM. SHOW
 CONDUIT SIZES AND THE GROUNDING
 ELECTRODE SYSTEM CONNECTIONS PER 250.50.
  
 2} PROVIDE LOAD CALCS AND PANEL
 SCHEDULES PER 215.5.
  
 3} SHOW FAULT CURRENT CALC AND INDICATE
 THE AIC RATING OF THE EQUIPMENT, 110.9.
  
 4} LOCATE OUTDOOR RECEPTACLE'S PER
 210.52(E).
  
 5} KITCHEN COUNTERTOP RECEPTACLE SPACING
 MUST COMPLY WITH 210.52(C).
  
 6} SHOW SMOKE DETECTOR LOCATIONS PER
 905.2.2 FBC & 8-1.4.1.6.2. NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  