Plan Review Notes For Permit 05021036 |
Permit Number |
05021036 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-18 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} COMPLETE THE RISER DIAGRAM. SHOW | | CONDUIT SIZES AND THE GROUNDING | | ELECTRODE SYSTEM CONNECTIONS PER 250.50. | | | | 2} PROVIDE LOAD CALCS AND PANEL | | SCHEDULES PER 215.5. | | | | 3} SHOW FAULT CURRENT CALC AND INDICATE | | THE AIC RATING OF THE EQUIPMENT, 110.9. | | | | 4} LOCATE OUTDOOR RECEPTACLE'S PER | | 210.52(E). | | | | 5} KITCHEN COUNTERTOP RECEPTACLE SPACING | | MUST COMPLY WITH 210.52(C). | | | | 6} SHOW SMOKE DETECTOR LOCATIONS PER | | 905.2.2 FBC & 8-1.4.1.6.2. NFPA-72. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|