Date |
Text |
2005-04-05 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| 1.) A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED, FS713.13. |
| |
| 2.) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE STAMPED |
| AND THE RECEIPT ATTACHED TO THE |
| APPLICATION.561-233-5025 |
| |
| 3.) NAILING FOR ROOF SHEATHING, 1-A6 AND |
| BB-A3 (6 IN OC) IS NOT COMPLIANT FOR |
| ZONE 3, FBC*TABLE 2306.1. |
| |
| 4.) ADDITIONAL FEES DUE TO VALUE |
| ADJUSTMENT.1888SF X 76.96, 513 X 41.6, |
| TOTAL OF 166640.SEE ATTACHED. |
| |
| 5.) WINDOW/DOOR BUCK DETAIL, A6, SHOWS |
| ATTACHMENT INTO WOOD FRAMING. OTHER |
| DETAILS SHOW THE CONSTRUCTION AS CBS. |
| |
| 6.) SPECIFY WINDOW AND DOOR SIZES. |
| BEDROOM WINDOWS ARE TO COMPLY WITH |
| EMERGENCY EGRESS REQUIREMENTS, |
| FBC1005.4. |
| |
| 7.) SIGN THE OWNER/AGENT LINE OF THE |
| ENERGY CALC. |
| |
| 8.) PROVIDE REACTION LOADS, ROOF FRAMING |
| PLAN. |
| |
| 9.) DOOR 2 BETWEEN LAUNDRY ROOM AND |
| GARAGE IS TO BE SOLID CORE, |
| FBC?13-403.1.ABCD. |
| |
| 10.) BB-A3 REFERS TO TRUSS PLAN FOR |
| GIRDER DETAIL.THIS WAS NOT PROVIDED. |
| NO CONNECTORS OR REACTION LOADS |
| SPECIFIED FOR GIRDER CONNECTIONS. |
| |
| 11.) AA-A3, PORCH DETAILS, REFERS TO |
| MECHANICAL PAGE. |
| |
| 12.) FLORIDA STATE PRODUCT APPROVAL DOES |
| NOT APPEAR TO MATCH THE NOA PROVIDED. |
| PROVIDE FLORIDA STATE PRODUCT APPROVAL |
| AND CIRCLE WHICH PRODUCT YOU ARE USING |
| |
| 13.) THE SAME DATA SHEETS WERE PROVIDED |
| FOR FL18 AND FL19.I CANNOT DETERMINE |
| COMPLIANCE WITH FAC9B72. |
| |
| 14.) THE TWO SPEC SHEETS SUBMITTED FOR |
| DOORS ARE FOR SINGLE DOORS.THE GLAZED |
| DOORS ON THE PLAN ARE DOUBLE DOORS. |
| |
| 15.) THE PLAN SHOWS A PANEL DOOR FOR THE |
| FRONT DOOR.THIS SERVES AS THE |
| EMERGENCY MEANS OF ESCAPE FBC1005.4.5. |
| IF THIS DOOR IS TO BE GLAZED, CHANGE THE |
| PANEL DOOR NOTE ON THE PLAN AND INDICATE |
| THE EMERGENCY MEANS OF ESCAPE. |
| |
| 16.) PRODUCT APPROVALS ALSO REQUIRED |
| FOR: |
| ROOF TILE |
| SHUTTERS |
| SINGLE HUNG WINDOWS |
| OPAQUE DOOR |
| |
| PRODUCT APPROVALS NOT APPROVED PRIOR TO |
| ISSUANCE WILL REQUIRE SEPARATE PERMITS |
| FOR THOSE ITEMS. |
| |
| 17.) COMPLETE A HURRICANE SHUTTER |
| INSTALLATION SCHEDULE, SEE ATTACHED. |
| |
| 18.) THIS PROPERTY IS IN THE FIRE |
| DISTRICT.DECLARE A BUILDING TYPE |
| FBC600.TYPE VI CONSTRUCTION NOT |
| ALLOWED IN THE FIRE DISTRICT, FBC*102.1. |
| |
| 19.) SHOW COMPLIANCE WITH FBC TABLE 600 |
| IN REGARDS TO FIRE RESISTANCE FOR |
| EXTERIOR BEARING WALLS. |
| |
| 20.) PROVIDE DESIGN CRITERIA FOR THE |
| TRUSSES, TCLL, TCDL, BCLL, BCDL.BCLL |
| TO COMPLY WITH FBC TABLE 1604.1. |
| |
| 21.)SHOW ATTIC ACCESS LOCATION AND |
| SIZE, FBC2309.6, 2309.7. |
| |
| 22.)32" CLEAR OPENING REQUIRED FOR THE |
| FRONT DOOR, FBC TABLE 1004. |