Plan Review Notes For Permit 05021030 |
Permit Number |
05021030 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-02 00:00:00 | | | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | CIRCUITS 1,3 AND 5 INCORRECTLY HAVE #14 | | WIRE ON A 20AMP BREAKER.310.16. | | | | A SMOKE DETECTOR IS REQUIRED IN THE HALL | | OUTSIDE OF THE BEDROOMS (2ND FL.) PER | | 905.2.2 FBC. | | | | MAKE CORRECTIONS ON THE DRAWING AND | | RESUBMIT PRIOR TO ROUGH ELECTRICAL | | INSPECTION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|