Plan Review Notes
Plan Review Notes For Permit 05021030
Permit Number 05021030
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-18 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT A COMPLETE RISER DIAGRAM, LOAD
 CALCULATIONS, AND PANEL SCHEDULES PER
 215.5.
  
 2} SHOW CALCULATIONS AND GIVE RATING FOR
 FAULT CURRENT AT THE SERVICE PER 110.9 &
 10, AND AIC RATING OF THE EQUIPMENT .
  
 3} A RECEPTACLE IS REQUIRED AT THE REAR
 OF THE HOUSE PER 210.52(E).
  
 4} BOTH FRONT AND REAR RECEPTACLES MUST
 BE GFI PER 210.8(A)(3).
  
 5} GARAGE RECEPTACLES MUST COMPLY WITH
 210.8(A)(2), GFI.
  
 6} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH THE SPACING
 REQUIREMENTS OF 210.52(C).
  
 7} PLEASE SEE THAT THE SMOKE DETECTORS
 COMPLY WITH LOCATION REQUIREMENTS OF
 905.2.2 FBC & 8-1.4.1.6.2. NFPA-72.
  
 8} SEVERAL ROOMS DO NOT COMPLY WITH THE
 SPACING REQUIREMENTS OF 210.52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  