Plan Review Notes For Permit 05021030 |
Permit Number |
05021030 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-18 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SUBMIT A COMPLETE RISER DIAGRAM, LOAD | | CALCULATIONS, AND PANEL SCHEDULES PER | | 215.5. | | | | 2} SHOW CALCULATIONS AND GIVE RATING FOR | | FAULT CURRENT AT THE SERVICE PER 110.9 & | | 10, AND AIC RATING OF THE EQUIPMENT . | | | | 3} A RECEPTACLE IS REQUIRED AT THE REAR | | OF THE HOUSE PER 210.52(E). | | | | 4} BOTH FRONT AND REAR RECEPTACLES MUST | | BE GFI PER 210.8(A)(3). | | | | 5} GARAGE RECEPTACLES MUST COMPLY WITH | | 210.8(A)(2), GFI. | | | | 6} THE KITCHEN COUNTERTOP RECEPTACLES | | MUST COMPLY WITH THE SPACING | | REQUIREMENTS OF 210.52(C). | | | | 7} PLEASE SEE THAT THE SMOKE DETECTORS | | COMPLY WITH LOCATION REQUIREMENTS OF | | 905.2.2 FBC & 8-1.4.1.6.2. NFPA-72. | | | | 8} SEVERAL ROOMS DO NOT COMPLY WITH THE | | SPACING REQUIREMENTS OF 210.52. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|