Plan Review Notes For Permit 05020882 |
Permit Number |
05020882 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-05-21 00:00:00 | PLUMBING PLANN REVIEW FBC 2001 FAILED, | | THIRD TIME. | | (1) PREVIOUS NOTES DATED 3-7-05 G S, | | 3-15-05 K S, NOT ADDRESSED. | | (2)SEC 104.2 DRAWINGS & SPECIFICATIONS: | | PROVIDE SUFFICENT INFORMATION, FOR | | CLARITY OF WORK. | | (3) 424.2.6.6.4 MAIN DRAIN: COMMON LINE | | TO PUMP WATER TO DRAIN SIMULTANEUOSLY. | | (4) 424.2.12 TEST: 35 PSI, NO AIR TEST. | | (5) 424.2.13.2 JOINTS, CONNECTIONS: FBCP | | 2001 SEC 605.21 PURPLE PRIMER PVC PIPE. | | (6) 424.2.6.2 LIST REQUIRED EQUIPMENT: | | (7) 424.2.7.3 PUMP CAPACITY:HP,GPM. | | (8)424.2.6.3 WATER VELOCITY: FPS. | | (9) ALL OF THE ABOVE TO BE ON PLANS, IN | | NOTES OR SPECIFIC COMMENTS. | | (10) SEE ATTACHED SHEET CONCERNING THE | | DESIGN PROFESSIONAL AND FS 533.80(2)(B) | | IF PLANS COME IN WITH THE SAME COMMENTS | | MORE THAN TWO TIMES 4X FEE WILL BE | | ATTACHED TO PLANS. | | QUESTIONS CONTACT, | | 561-805-6692 PAUL SCHMITZ |
|