Plan Review Notes
Plan Review Notes For Permit 05020882
Permit Number 05020882
Review Stop P
Sequence Number 3
Notes
Date Text
2005-05-21 00:00:00PLUMBING PLANN REVIEW FBC 2001 FAILED,
 THIRD TIME.
 (1) PREVIOUS NOTES DATED 3-7-05 G S,
 3-15-05 K S, NOT ADDRESSED.
 (2)SEC 104.2 DRAWINGS & SPECIFICATIONS:
 PROVIDE SUFFICENT INFORMATION, FOR
 CLARITY OF WORK.
 (3) 424.2.6.6.4 MAIN DRAIN: COMMON LINE
 TO PUMP WATER TO DRAIN SIMULTANEUOSLY.
 (4) 424.2.12 TEST: 35 PSI, NO AIR TEST.
 (5) 424.2.13.2 JOINTS, CONNECTIONS: FBCP
 2001 SEC 605.21 PURPLE PRIMER PVC PIPE.
 (6) 424.2.6.2 LIST REQUIRED EQUIPMENT:
 (7) 424.2.7.3 PUMP CAPACITY:HP,GPM.
 (8)424.2.6.3 WATER VELOCITY: FPS.
 (9) ALL OF THE ABOVE TO BE ON PLANS, IN
 NOTES OR SPECIFIC COMMENTS.
 (10) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 533.80(2)(B)
 IF PLANS COME IN WITH THE SAME COMMENTS
 MORE THAN TWO TIMES 4X FEE WILL BE
 ATTACHED TO PLANS.
 QUESTIONS CONTACT,
 561-805-6692 PAUL SCHMITZ