2005-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS HAVE 2 POOL LAYOUTS AND 2
 ENGINEERS OF RECORD. SHE 2 OF 3 SHOWS 4
 POOL RETURNS, 2 WALL MAIN DRAINS AND 2
 FLOOR MAIN DRAINS. SHT 1 OF 1 SHOWS NO
 POOL RETURNS, AND ALL MAIN DRAINS ON THE
 WALLS. PLEASE CLARIFY. SECTION 104.2.1.
 2) ALL SHEETS BY GATOR ENGINEERING,
 ENGINEER SHALL INDICATE THEIR NAME,
 ADDRESS, AND LICENSE NUMBER ON EACH
 SHEET. ENGINEERS PRINTED NAME AND
 LICENSE NUMBER ARE MISSING. FAC
 61G14-23.002(2) & FS 471.025
 3) SHT 1 OF 1 PIPING DIAGRAM DOES NOT
 SHOW THE VENTS FOR THE MAIN DRAINS, NOR
 DOES IT SHOW A RETURN TO THE POOL FROM
 THE RECIRCULATION PUMB. SECTION 104.2.1.
 4) PLANS BY GATOR ENGINEERING INDICATE
 NO POOL HEATER, BUT PLANS BY BEA
 ENGINEERING SHOW A POOL HEATER ON THE
 PIPING DIAGRAM, PLEASE CLARIFY. SECTION
 104.2.1.
  