Plan Review Notes For Permit 05020882 |
Permit Number |
05020882 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-07 00:00:00 | 3/7/05 | | | | 1-PER DUAL MAIN DRAIN ATMOSPHERIC VENT | | ARRANGMENT SH 3.MAIN DRAIN SHALL REFLECT | | VENT ARRANGEMENT.MAIN DRAIN SHALL DRAIN | | SIMULTANEOUSLY.SUCTION LINE SHALL TIE IN | | | | AT CENTER OF THE DRAINS.VENT LINETO TIE | | INTO SUCTION LINE 12" FROM DRAIN TIE IN, | | PER VENT ARRANGEMENT. | | 2-SPA LAYOUTS ON SHEETS 1-2 INDICATE | | MAIN DRAINS ON FLOOR.SPA PLAN ON SHEET | | 1 OF 1 INDICATE MAIN DRAINS ON WALL. | | PLEASE CORRELATE PLANS. | | 3-PIPING DIAGRAM SHEET 1 OF 1 DOES NOT | | SHOW A RETURN LINE FROM 2ND PUMP,PLEASE | | CLARIFY. |
|