Plan Review Notes For Permit 05020807 |
Permit Number |
05020807 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-31 00:00:00 | DENIED; | | ADDITONAL WORK BEING DONE WAS NOT PART | | OF ORIGINAL SCOPE OF WORK. ADDITIONAL | | FEE'S DUE. | | MED-GAS APPLICATION # 05060902 WAS | | REVIEW ON 6/28/05 AND DENIED. (COPY OF | | REVIEW ATTACHED) | | ADDITIONAL NOTES; | | 1.PAGE A-3 NOTE 5 VACUUM LINES SHALL BE | | SUPPORTED EVERY 4' PER FBC PLUMBING | | TABLE 308.5 | | 2.CUT SHEET FOR STERI-CENTER IS NOT | | LEGIBLE, PLEASE RESUBMIT. | | 3.MANUFACTORS INSTALLATION INSTRUCTIONS | | ARE NOT TO CODE NFPA SEC 5.3.3.6.3.1. | | (MUST BE DIRECTLY PIPED TO SANITARY | | SYSTEM. | | 4.PIPING RISER DIAGRAM DOES NOT SHOW A | | TRAP FOR OVER HEAD VACUUM LINE AS SHOWN | | IN THE INSTALLATION INSTRUCTIONS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|