Plan Review Notes
Plan Review Notes For Permit 05020785
Permit Number 05020785
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-23 00:00:00 
 PLEASE NOTE THAT TWO DEMAND FACTORS WERE
 USED IN THE LOAD CALCULATION. IF 220.32
 IS USED THEN PART III CANNOT BE. USE ONE
 OR THE OTHER AND ADJUST CONDUIT RISER,
 CONDUCTOR AND GEC SIZES, RESUBMIT FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  