Plan Review Notes
Plan Review Notes For Permit 05020768
Permit Number 05020768
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-16 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 FOR MIN CIRCUITS REQUIRED PER 2002 NEC.
 BATHS, 210.11C3, KITCHEN 210.52/210.11C1
 WASHER 220.16, 210.52 ETC.
 215.5
  
 2)NOTE: PLEASE SEE SD'S, INSIDE AND
 OUTSIDE BEDRMS WILL BE REQUIRED.
 NFPA-72 8-1.4.1.6.2
 PLEASE SEE EGRESS LT PER 210.70 WILL BE
 REQUIRED.
 PLEASE SEE ARC FAULT PROTECTION REQUIRED
 PER 210.12.
  
 PLEASE SEE PLANS HAVE BEEN REDLINED FOR
 LOCATIONS OF REQUIRED ITEMS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  