2005-10-03 00:00:00 | *** NOTES/ PROVISO*** | | | | PLEASE SEE SMALL APPLIANCE CIRCUITS | | SHOWN AT 1.0KW? | | PLEASE SEE NEC 210.11C1, 1.5KW MIN. | | PLEASE REVISE AND ADJUST LOAD | | CALCULATIONS BEFORE FINAL ALONG WITH ANY | | OTHER REVISIONS. |
|