Plan Review Notes
Plan Review Notes For Permit 05020544
Permit Number 05020544
Review Stop M
Sequence Number 1
Notes
Date Text
2005-02-25 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED W/NOTIFICATION PER 2001
 FBC(M)606.2.1 & 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved