2005-04-15 00:00:00THIRD CHECKLIST:
 1- TRUSS ANCHOR SCHEDULE:
 A) CONNECTOR #5 HUSC412 COULD NOT BE
 FOUND IN THE CATALOGUE.
  
 B) COPIES OF SIMPSON CATALOGUE SUBMITTED
 CLEARLY INDICATE THAT THESE ARE WOOD TO
 WOOD CONNECTORS. AND , NONE OF THEM IS A
 HUSC412.
  
 C) NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. SEE SIMPSON CATALOGUE FOR
 WOOD TO MASONRY APPLICATIONS.
  
 D) CONNECTOR #5 HUSC412 SHOWN ON THE
 CONNECTOR SCHEDULE CALLS FOR 10 TAPCONS,
 WHILE FOOTNOTE **CALLS FOR 12 TAPCONS.
 INFORMATION DOESN'T MATCH.
  
 E) ON PREVIOUS CHECKLIST IT WAS
 REQUESTED TO UPDATE TRUSS ANCHOR
 SCHEDULE BY CHECKING USP/SIMPSON LATEST
 CATALOGUES WHICH WERE REVISED TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001. OR,
 OTHERWISE, TO PROVIDE COMPLETE
 ENGINEERING CALCULATIONS SHOWING
 COPMPLIANCE WITH SEC. 1609.4.3 FBC WHEN
 TYPE AND NUMBER OF NAILS ARE DIFFERENT
 THAN THOSE ALREADY TESTED AND PUBLISHED
 BY THE MANUFACTURER.
 THIS WAS NOT DONE. PROVIDE COMPLETE
 ENGINEERING CALCULATIONS SHOWING HOW
 DOES CONNECTOR #5 PROVIDE SPECIFIED
 LOADS USING 10 (OR 12) TAPCONS 3/16 X 2
 1/4, WHILE 2005 SIMPSON CATALOGUE PAGE
 128 SHOWS CONNECTOR HU410 (WHICH IS THE
 CONNECTOR THAT NEEDS TO BE SPECIFIED FOR
 THE DESIRED APPLICATION) SHOWS THAT
 USING 18 TITEN 1/4 X 2 3/4 WILL BE GOOD
 FOR 1505 UPLIFT.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
  
 F) CALLED SIMPSON COMPANY AND WAS TOLD
 THAT THE "S" SPECIFIED ON CONNECTORS HUS
 STANDS FOR SHEAR. CONNECTOR HUS412 WAS
 TESTED FOR SHEAR IN WOOD TO WOOD
 APPLICATIONS AND NOT IN WOOD TO MASONRY
 APPLICATIONS. THEREFORE, THIS
 ADDITTIONAL LOAD SHALL NOT BE CONSIDERED
 IN MASONRY CONNECTORS. THEREFORE,
 CONNECTOR SHALL NOT HAVE THE "S" WHEN
 SPECIFIED FOR MASONRY APPLICATION.
  
 G) REVIEWALL TRUSS ANCHOR SCHEDULE AND
 FOOTNOTES AND REVISE/UPDATE AS REQUIRED
 TO MEET MANUFACTURER TESTED & PUBLISHED
 VALUES OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS WHEN DEVIATING FROM THE
 CATALOGUE. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 2- SURVEY SUBMITTED DOESN'T MATCH PLANS.
 A) IT DOESN'T INCLUDE THE COVERED PORCH.
 B) DIMENSIONS SHOWN ON SURVEY DON'T
 MATCH PLANS. IDENTIFY WHICH DIMENSIONS
 ARE CORRECT. THE ONES IN THE SURVEY OR
 THE ONES IN PLANS AND REVISE AS REQ'D.
  
 3- MISSING FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS. NOT SUBMITTED THIS TIME.
 B) SINGLE FRENCH DOORS AS SHOWN ON
 PLANS. PRODUCT APPROVAL SUBMITTED IS FOR
 DOUBLE DOORS WITH SIDELITES OR SINGLE
 DOOR WITH SIDELITES.
  
 4- NEED TO REVISE DETAIL FOR ARCHED
 WINDOWS. SEE ARCHED WINDOW PRODUCT
 APPROVAL FOR SPACING REQUIRED TO FASTEN
 WINDOW TO STRUCTURAL BUCK AND REVISE 2X4
 BLOCKING SPACING REQUIRED TO RECEIVE
 WINDOW FASTENERS.
  
 5- OWES $3552.55 WHICH WAS NOT PAID AT
 TIME OF PERMIT APLICATION PLUS
 RE-SUBMITTAL FEES.
  