2005-04-15 00:00:00 | THIRD CHECKLIST: |
| 1- TRUSS ANCHOR SCHEDULE: |
| A) CONNECTOR #5 HUSC412 COULD NOT BE |
| FOUND IN THE CATALOGUE. |
| |
| B) COPIES OF SIMPSON CATALOGUE SUBMITTED |
| CLEARLY INDICATE THAT THESE ARE WOOD TO |
| WOOD CONNECTORS. AND , NONE OF THEM IS A |
| HUSC412. |
| |
| C) NEED TO SPECIFY WOOD TO MASONRY |
| CONNECTOR. SEE SIMPSON CATALOGUE FOR |
| WOOD TO MASONRY APPLICATIONS. |
| |
| D) CONNECTOR #5 HUSC412 SHOWN ON THE |
| CONNECTOR SCHEDULE CALLS FOR 10 TAPCONS, |
| WHILE FOOTNOTE **CALLS FOR 12 TAPCONS. |
| INFORMATION DOESN'T MATCH. |
| |
| E) ON PREVIOUS CHECKLIST IT WAS |
| REQUESTED TO UPDATE TRUSS ANCHOR |
| SCHEDULE BY CHECKING USP/SIMPSON LATEST |
| CATALOGUES WHICH WERE REVISED TO COMPLY |
| WITH SEC. 1609.4.3 FBC 2001. OR, |
| OTHERWISE, TO PROVIDE COMPLETE |
| ENGINEERING CALCULATIONS SHOWING |
| COPMPLIANCE WITH SEC. 1609.4.3 FBC WHEN |
| TYPE AND NUMBER OF NAILS ARE DIFFERENT |
| THAN THOSE ALREADY TESTED AND PUBLISHED |
| BY THE MANUFACTURER. |
| THIS WAS NOT DONE. PROVIDE COMPLETE |
| ENGINEERING CALCULATIONS SHOWING HOW |
| DOES CONNECTOR #5 PROVIDE SPECIFIED |
| LOADS USING 10 (OR 12) TAPCONS 3/16 X 2 |
| 1/4, WHILE 2005 SIMPSON CATALOGUE PAGE |
| 128 SHOWS CONNECTOR HU410 (WHICH IS THE |
| CONNECTOR THAT NEEDS TO BE SPECIFIED FOR |
| THE DESIRED APPLICATION) SHOWS THAT |
| USING 18 TITEN 1/4 X 2 3/4 WILL BE GOOD |
| FOR 1505 UPLIFT. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| 2001. |
| |
| F) CALLED SIMPSON COMPANY AND WAS TOLD |
| THAT THE "S" SPECIFIED ON CONNECTORS HUS |
| STANDS FOR SHEAR. CONNECTOR HUS412 WAS |
| TESTED FOR SHEAR IN WOOD TO WOOD |
| APPLICATIONS AND NOT IN WOOD TO MASONRY |
| APPLICATIONS. THEREFORE, THIS |
| ADDITTIONAL LOAD SHALL NOT BE CONSIDERED |
| IN MASONRY CONNECTORS. THEREFORE, |
| CONNECTOR SHALL NOT HAVE THE "S" WHEN |
| SPECIFIED FOR MASONRY APPLICATION. |
| |
| G) REVIEWALL TRUSS ANCHOR SCHEDULE AND |
| FOOTNOTES AND REVISE/UPDATE AS REQUIRED |
| TO MEET MANUFACTURER TESTED & PUBLISHED |
| VALUES OR PROVIDE COMPLETE ENGINEERING |
| ANALYSIS WHEN DEVIATING FROM THE |
| CATALOGUE. SECTION 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 2- SURVEY SUBMITTED DOESN'T MATCH PLANS. |
| A) IT DOESN'T INCLUDE THE COVERED PORCH. |
| B) DIMENSIONS SHOWN ON SURVEY DON'T |
| MATCH PLANS. IDENTIFY WHICH DIMENSIONS |
| ARE CORRECT. THE ONES IN THE SURVEY OR |
| THE ONES IN PLANS AND REVISE AS REQ'D. |
| |
| 3- MISSING FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) ENTRY DOORS. NOT SUBMITTED THIS TIME. |
| B) SINGLE FRENCH DOORS AS SHOWN ON |
| PLANS. PRODUCT APPROVAL SUBMITTED IS FOR |
| DOUBLE DOORS WITH SIDELITES OR SINGLE |
| DOOR WITH SIDELITES. |
| |
| 4- NEED TO REVISE DETAIL FOR ARCHED |
| WINDOWS. SEE ARCHED WINDOW PRODUCT |
| APPROVAL FOR SPACING REQUIRED TO FASTEN |
| WINDOW TO STRUCTURAL BUCK AND REVISE 2X4 |
| BLOCKING SPACING REQUIRED TO RECEIVE |
| WINDOW FASTENERS. |
| |
| 5- OWES $3552.55 WHICH WAS NOT PAID AT |
| TIME OF PERMIT APLICATION PLUS |
| RE-SUBMITTAL FEES. |
| |