Date Text
2005-04-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOT DOES IT
 MEET CODE REQUIREMENTS:
 A) WASH MACHINE IS NOT VENTED, AND AS
 DRAWN THE TRAP IS UNDER THE SLAB.
 SECTION 901.2.1.
 B) SHOWER BATH NEXT TO KITCHEN SANT.
 RISER DOES NOT REFLECT THE PIPING SHOWN
 ON SHT P-1. SEE RED LINE CORRECTIONS TO
 REFLECT FLOOR PLAN. SECTION 104.2.1.
 C) VENT FOR W/C IN MASTER BATH IS A
 HORIZONTAL DRY VENT IF PIPED AS SHOWN.
 SECTIONS 905.3 & 905.4
 D) SHOWER IN MASTER BATH SHALL BE TO
 THE RIGHT OF THE BRANCH LINE TO REFLECT
 THE FLOOR PLAN SHT P-1. SECTION 104.2.1.
 E) THE SIZE OF THE DRAINAGE PIPING SHALL
 NOT BE REDUCED IN SIZE IN THE DIRECTION
 OF FLOW. SECTION 704.2 (SEE PIPE SIZE
 DOWNSTREAM OF THE M/B W/C).
 (SEE ALL REDLINE COMMENTS, CORRECTIONS,
 AND EXAMPLES ON ONE SET OF PLANS)
 2) SHT P-1 PLUMBING NOTES #12, AIR
 CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE FROM NOTES.
 3) PLUMBING GENERAL NOTES #1 INDICATE
 COMPLIANCE WITH MARTIN COUNTY
 AMMENDMENTS. THE PLANS SHALL BE IN
 COMPLIANCE WITH CITY OF W.P.B. CORRECT
 REFERENCE.
  
 CORRECT PLANS AND RESUBMIT FOR REVIEW.
  