2005-04-02 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1) SHT P-2 SANITARY RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOT DOES IT |
| MEET CODE REQUIREMENTS: |
| A) WASH MACHINE IS NOT VENTED, AND AS |
| DRAWN THE TRAP IS UNDER THE SLAB. |
| SECTION 901.2.1. |
| B) SHOWER BATH NEXT TO KITCHEN SANT. |
| RISER DOES NOT REFLECT THE PIPING SHOWN |
| ON SHT P-1. SEE RED LINE CORRECTIONS TO |
| REFLECT FLOOR PLAN. SECTION 104.2.1. |
| C) VENT FOR W/C IN MASTER BATH IS A |
| HORIZONTAL DRY VENT IF PIPED AS SHOWN. |
| SECTIONS 905.3 & 905.4 |
| D) SHOWER IN MASTER BATH SHALL BE TO |
| THE RIGHT OF THE BRANCH LINE TO REFLECT |
| THE FLOOR PLAN SHT P-1. SECTION 104.2.1. |
| E) THE SIZE OF THE DRAINAGE PIPING SHALL |
| NOT BE REDUCED IN SIZE IN THE DIRECTION |
| OF FLOW. SECTION 704.2 (SEE PIPE SIZE |
| DOWNSTREAM OF THE M/B W/C). |
| (SEE ALL REDLINE COMMENTS, CORRECTIONS, |
| AND EXAMPLES ON ONE SET OF PLANS) |
| 2) SHT P-1 PLUMBING NOTES #12, AIR |
| CHAMBERS ARE NOT APPROVED. DELETE |
| REFERENCE FROM NOTES. |
| 3) PLUMBING GENERAL NOTES #1 INDICATE |
| COMPLIANCE WITH MARTIN COUNTY |
| AMMENDMENTS. THE PLANS SHALL BE IN |
| COMPLIANCE WITH CITY OF W.P.B. CORRECT |
| REFERENCE. |
| |
| CORRECT PLANS AND RESUBMIT FOR REVIEW. |
| |