2005-02-18 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} THE WHIRLPOOL MUST BE GFI PROTECTED
 PER 680.43(A)(3)NEC.
  
 2} THE WHIRLPOOL IS NOT LISTED ON THE
 PANEL SCHEDULE.
  
 3} RECEPTACLES NEED TO BE ADDED TO THE
 KITCHEN COUNTERTOP TO COMPLY WITH
 SPACING REQUIREMENTS OF 210.52(C)(1).
  
 4} THE DISCONNECT FOR CU#2 DOES NOT
 APPEAR TO HAVE CLEARANCE PER 110.26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  