2005-03-04 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- EAST ELEVATION EXCEEDS MAXIMUM |
| PERCENTAGE OF OPENING ALLOWED BY TABLE |
| 600 FBC 2001 AT GARDEN COURT. |
| |
| 2- PROVIDE DESIGN SPECS FOR 30PSF ATTIC |
| LIVE LOAD AS REQUIRED BY TABLE 1604.1 |
| FBC 2001. |
| |
| 3- LAYOUT SHOWN ON SURVEY DOESN'T MATCH |
| PLANS. REVISE AS REQUIRED. |
| |
| 4- AN EGRESS EASEMENT (3'-0" MIN.) NEED |
| TO BE RECORDED IN THE COUNTY RECORDS |
| WHENUSING ADJOINING LOT FOR EGRESS AS |
| REQUIRED BY THE BUILDING OFFICIAL. |
| |
| 5- PROVIDE COMPLETE SPECS/DETAILS FOR |
| CEILING INSTALLATION AT ENTRY AND REAR |
| PORCHES. SPECIFY FASTENER TYPE AND |
| SPACING AS REQUIRED BY ASTM C-926 AND |
| ASTM C-1063. SEC. 2504.2 FBC 2001. |
| |
| 6- PROVIDE COMPLETE BATHROOM (POWDER |
| ROOM IS NOT A COMPLETE BATHROOM) WITH |
| DOOR THAT ALLOWS 29" MIN. CLEAR OPENING |
| AS REQ'D BY SEC. 11-11 FBC 2001. |
| |
| 7- PROVIDE FIREPLACE UL LISTING AND |
| COMPLETE SPECS AS REQUIRED BY SECTION |
| 2806 FBC 2001. |
| |
| 8- PROVIDE KNEE WALL SECTION/DETAIL AT |
| ENTRY PORCH SPECIFYING ALL FASTENERS. |
| SECTION 104.2.1.2 CITY AMENDMENTS TO FBC |
| |
| |
| 9- SPECIFY SIZE OF CONTINUOUS |
| VENTILATION AT ATTIC AREA AND HOOD ROOF |
| SCREEN. SEC. 2309.7 FBC 2001. |
| |
| 10- PRIVACY WALL FOOTING AT GARDEN COURT |
| IS ENCROACHING INTO ADJACENT PROPERTY. |
| REVISE AS REQUIRED. |
| |
| 11- CLARIFY SIZE OF INTERIOR BEARING |
| WALL. 2X4'S OR 2X6'S? SEE SHEET S-2. |
| |
| 12- SPECIFY CONNECTORS AT THE ENDS OF |
| ENTRY PORCH BEAM. SECTION 104.2.1.2 OF |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 13- CLARIFY WHICH METHOD OF GLASS |
| PROTECTION IS GOING TO BE USED: SHUTTERS |
| OR MISSILE IMPACT GLAZING ON DOORS AND |
| WINDOWS. BOTH WERE SUBMITTED. |
| **PROVIDE COMPLETE INFORMATION FOR |
| EITHER OPTION WITH LEGIBLE DRAWINGS. |
| |
| 14- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) "INSWING" ENTRY DOORS. SEE PLANS. |
| B) USP USC63 TRUSS CONNECTOR. |
| C) SLIDING GLASS DOORS (DWGS SUBMITTED |
| WITH FLORIDA PRODUCT APPROVAL ARE FOR |
| FRENCH DOORS). |
| D) SAME DRAWINGS FOR THERMA-TRU DOORS |
| THAT WERE SUBMITTED FOR FLORIDA PRODUCT |
| APPROVAL. |
| E) SMALL AND LARGE GARAGE DOORS WITH |
| LEGIBLE DRAWINGS. |
| F) WINDOW MULLIONS.(DRAWINGS SUBMITTED |
| ARE FOR SLIDING GLASS DOORS). |
| |
| 15- BBQ GRILL SPECIFICATIONS DOESN'T |
| ALLOW TO BUILD GRILL UNDER UNPROTECTED |
| COMBUSTIBLE CONSTRUCTION AND UNIT IS FOR |
| OUTDOOR USE ONLY. PROVIDE MANUFACTURER'S |
| |
| SPECS THAT ALLOW INSTALLATION OF GRILL |
| IN THE PORCH. |
| |
| 16- REVISE GENERAL NOTES ON SHEET A-1. |
| STUCCO ON METHAL LATH TO BE 7/8" MIN. AS |
| REQUIRED BY ASTM C-926. |
| SAFETY GLASS TO COMPLY WITH ANZI Z97.1, |
| NOT ABS1-Z97.1. |
| |
| 17- TYPICAL EXTERIOR WALL SEC. HAS 2 |
| DIFFERENT SPECS FOR ROOF SHEATHING |
| NAILING. CLARIFY SPACING OF NAILS. SEE |
| COMMENTS AND TABLE 2306.1 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 18- CONNECTOR #3 SPECIFIED ON ROOF |
| FRAMING PLAN DOESN'T RESIST THE 2717# |
| UPLIFT LOAD CALCULATED BY THE ENTRY |
| PORCH GIRDER TRUSS. REVISE AS REQ'D. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 19- PROVIDE COMPLETE DETAIL FOR FRAMING |
| OF ARCHED OPENINGS TO RECEIVE WINDOWS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 20- TYPICAL CMU PIER DETAIL: SPECIFY |
| SIZE OF FOOTING AND EMBEDMENT BELOW |
| GRADE. SPECIFY PIER HEIGHT. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 21- PLEASE PROVIDE ONLY THE DETAILS THAT |
| APPLY TO THIS PROJECT TO EXPEDITE REVIEW |
| PROCESS AND AVOID CONFLICTS. |
| |
| 22- NEED RECORDED NOTICE OF COMMENCEMENT |
| |
| 23- OWES $3552.55 FOR PERMIT. PERMIT |
| FEES WERE NOT PAID AT TIME OF |
| APPLICATION. |
| |