Plan Review Notes
Plan Review Notes For Permit 05020218
Permit Number 05020218
Review Stop M
Sequence Number 1
Notes
Date Text
2005-02-14 00:00:00DENIED:
 1.PLAN SHEET A-2.0 INDICATES A
 LOUVERED VENT AT THE BOTTOM OF THE DOOR
 AND ABOVE THE HEADER INTO THE LAUNDRY
 ROOM.PLEASE CLARIFY THE FOLLOWING:
 A) WILL THIS BE FOR THE COMBUSTION AIR?
 B) THIS INSTALLATION WILL TRANSFER TOXIC
 FUMES FROM THE GARAGE INTO THE LAUNDRY
 ROOM AND INTO THE LIVING AREA.
 C) INDICATE SIZE OF LOUVERS.
  
 2.PLEASE PROVIDE MANUFACTURER'S
 SUBMITTAL & INSTALLATION INSTRUCTIONS
 FOR THE DRYER AND WATER HEATER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.