Plan Review Notes
Plan Review Notes For Permit 05020215
Permit Number 05020215
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-01 00:00:00********* UNSAT 2ND REVIEW ***********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES DUE TO CHANGES
 ON PLANS.
  
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 NO, PLEASE SEE
 COUNTERSPACE REDLINED.
 PLEASE ALSO SEE 210.52C1 FOR SPACING.
 PLEASE ALSO SEE NEW NOTES BELOW.
  
 4)NOTE: NO, PREVIOUS NOTES AND NOTE #3
 ABOVE.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK
  
 9)NOTE: NOTE #9 NO, PLEASE SEE REDLINED
 2' OF WALL IN BEDRM #5.
  
 10)NOTE: NOTE #10 NO, PLEASE SEE RISER
 SHOWS REQUIRED GROUNDING ELECTRODE
 ATTACHMENTS AS "OPTIONS". PLEASE SEE
 250.50, THESE ARE REQUIRED.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 OK.
  
 NEW NOTES:
  
 1)NOTE: PLEASE CORRRELATE WIRE SIZES FOR
 SUB PANEL "B". PLEASE SEE PANEL "A",
 SHOWS 80A BRKR ON #12 AWG WHICH IS RATED
 AT 20A'S PER 310.16
  
 2)NOTE: PLEASE SEE CIRCUITING FOR
 CIRCUIT #23, THIS IS SHOWN ON MANY GEN
 RECEPT/LIGHTING, SMALL APPLIANCE
 COUNTERSPACE AND IS ALSO SHOWN FOR ONE
 PHASE OF OVEN.
 PLEASE REVISE AND ADJUST CIRCUITING.
  
 3)NOTE: PLEASE SEE CIRCUITING FOR CU,
 SHOWN AS "B 1,2, PLEASE SEE THIS SHOWS
 BOTH LEGS FROM THE SAME PHASE. (A).
 PLEASE SEE PANEL SCHEDULE. #1&3??
 (MISPRINT)
  
 4)NOTE: PLEASE SEE PANEL "B" IS NOW
 SHOWN BEHIND A/C CU.
 PLEASE SEE 110.26 FOR MIN CLEARENCE FOR
 PANEL AND A/C DISCONNECT.
  
 5)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 6)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL AND
 COMMENTS WHICH ARE REPEATED AFTER THREE
 REVIEWS. THIS IS ONLY GIVEN AS A NOTICE
 AT THIS TIME.
  
 PLEASE SEE PLANS, ALL OF THE ABOVE ITEMS
 HAVE BEEN REDLINED FOR AREAS OF NOTES.
  
 PLEASE REMOVE ALL OL/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW