2005-02-11 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRM
 AND PANEL "M".
 PLEASE SEE RISER INDICATES AS METER/MAIN
 COMBO WITH 200A MAIN BREAKER AND FEED
 THRU LUGS, HOWEVER PANEL "M" IS SHOWN AS
 225A MLO W/ A 200A BRKR FEEDING
 PANEL"A".?
 PLEASE SEE RISER SHOWS 1/0'S (RATED AT
 150A'S) AS THE "FEED-THRU" CONDUCTORS
 WHICH ARE PROTECTED BY A 200A BRKR.
 310.16/310.15B6
 PLEASE SEE PANEL SCHEDULE "M" SHOWS
 3/0'S FEEDING PANEL "A"??
 PLEASE ALSO SEE PANEL "M" CONTAINS MORE
 THAN 6 POSSIBLE MAINS, WHICH IS NOT
 PERMITTED UNDER 230.71A
 PLEASE PROVIDE A MCB AS SHOWN ON RISER.
  
 2)NOTE: PLEASE SEE CIRCUITING FOR SD'S
 WHICH IS #21. PLEASE SEE 210.12 UNDER
 2002 NEC. SD'S ARE ALSO REQUIRED TO BE
 ON AN ARC FAULT PROTECTED CIRCUIT.
 PLEASE SEE CIRCUIT #21 IS ALSO SHOWN AS
 "WATER HEATER" CIRCUIT.
  
  
 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 4)NOTE: PLEASE SEE MISSINGREQUIRED
 GFI'S AT ISLNAD PER 210.8A6(PREVIOUS
 NOTE) AND ALSO SPACING PER 210.52C1-5
  
 5)NOTE: PLEASESEE RECEPT SHOWN ON
 SMALL APPL CIRCUIT WHICH IS NOT PART OF
 DINING RM.(MORNING RM)? A-13.
 THIS MAY NOT BE ON SAME CIRCUIT.
 210.52B
  
 6)NOTE: PLEASE SEE 210.52D.
 IN DWELLING UNITS, AT LEAST ONE WALL
 RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 900 MM (3 FT) OF THE
 OUTSIDE EDGE OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A
 WALL OR PARTITION THAT IS ADJACENT TO
 THE BASIN OR BASIN COUNTERTOP.
  
 7)NOTE: PLEASE SEE PLANS INDICATE A "GAS
 WATER HEATER", YET PANEL SCHEDULE
 INDICATES ELECTRIC?
 PLEASE CORRELATE.
  
 8)NOTE: PLEASE SEE "NOTES" #15, MENTIONS
 250.60 FOR NEUTRAL/GROUNDING FOR RANGES
 AND DRYERS. PLEASE SEE THIS ART IS FROM
 A PREVIOUS CODE. WE ARE NOW UNDER 2002
 NEC. THIS IS NOW 250.140
  
 9)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING IN BDRM #5 AND DINING RM.
  
 10)NOTE: PLEASE SEE RISER MENTIONS
 GROUNDING ELECTRODE "OPTIONS". PLEASE
 SEE 250.50 FOR MIN REQUIRED. FOOTER
 STEEL AND CWP (IF METAL) IS NOT AN
 OPTIONAL CONNECTION POINT.PLEASE
 ADJUST NOTE.
  
 11)NOTE: PLEASE SEE FS 481.025 WHICH
 REQUIRES PLANS TO BE SIGNED WITH LEGAL
 SIGNATURE. PLANS APPEAR TO BE "SIGNED"
 WITH AN INITIAL? IF THIS IS THE LEGAL
 SIGNATURE, PLEASE PROVIDE A SIGNED,
 DATED AND SEALED NOTORIZED LETTER TO
 ATTEST THIS AS YOUR LEGAL SIGNATURE.
 THIS WILL BE PLACED IN SIGNATURE FILE
 FOR ANY NEED OF FUTURE REFERENCE.
 WE HAVE HAD A PROBLEM, WITH PLANS
 FORGED, SEALS STOLEN ETC.
  
 12)NOTE: PLEASE SEE CODE REFERENCES FOR
 SD'S ARE FROM THE 1996 NFPA-72. PLEASE
 SEE WE ARE CURRNETLY UNDER THE 1999
 NFPA-72. THESE REFERENCES SHOULD READ
 8-1.4.1.6.2, 8-1.4.2 FOR SD
 REQUIREMENTS
  
 PLEASE SEE MOST OF THE ABOVE HAS BEEN
 REDLINED ON ONE SET OF PLANS FOR AREAS
 OF NOTES ABOVE.
  
 ***PLEASE REMOVE ANY/ ALL OLD VOIDED
 SHEETS AND INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 * ADDED NOTE ****
  
 PLEASE SEE CIRCUIT FOR WHIRLPOOL TUB
 SHOWS GFI PROTECTION OPTIONAL?
 PLEASE SEE 680.71