Date |
Text |
2005-02-11 00:00:00 | *********** UNSAT **************** |
| |
| 1)NOTE: PLEASE CORRELATE RISER DIAGRM |
| AND PANEL "M". |
| PLEASE SEE RISER INDICATES AS METER/MAIN |
| COMBO WITH 200A MAIN BREAKER AND FEED |
| THRU LUGS, HOWEVER PANEL "M" IS SHOWN AS |
| 225A MLO W/ A 200A BRKR FEEDING |
| PANEL"A".? |
| PLEASE SEE RISER SHOWS 1/0'S (RATED AT |
| 150A'S) AS THE "FEED-THRU" CONDUCTORS |
| WHICH ARE PROTECTED BY A 200A BRKR. |
| 310.16/310.15B6 |
| PLEASE SEE PANEL SCHEDULE "M" SHOWS |
| 3/0'S FEEDING PANEL "A"?? |
| PLEASE ALSO SEE PANEL "M" CONTAINS MORE |
| THAN 6 POSSIBLE MAINS, WHICH IS NOT |
| PERMITTED UNDER 230.71A |
| PLEASE PROVIDE A MCB AS SHOWN ON RISER. |
| |
| 2)NOTE: PLEASE SEE CIRCUITING FOR SD'S |
| WHICH IS #21. PLEASE SEE 210.12 UNDER |
| 2002 NEC. SD'S ARE ALSO REQUIRED TO BE |
| ON AN ARC FAULT PROTECTED CIRCUIT. |
| PLEASE SEE CIRCUIT #21 IS ALSO SHOWN AS |
| "WATER HEATER" CIRCUIT. |
| |
| |
| 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| 4)NOTE: PLEASE SEE MISSINGREQUIRED |
| GFI'S AT ISLNAD PER 210.8A6(PREVIOUS |
| NOTE) AND ALSO SPACING PER 210.52C1-5 |
| |
| 5)NOTE: PLEASESEE RECEPT SHOWN ON |
| SMALL APPL CIRCUIT WHICH IS NOT PART OF |
| DINING RM.(MORNING RM)? A-13. |
| THIS MAY NOT BE ON SAME CIRCUIT. |
| 210.52B |
| |
| 6)NOTE: PLEASE SEE 210.52D. |
| IN DWELLING UNITS, AT LEAST ONE WALL |
| RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| BATHROOMS WITHIN 900 MM (3 FT) OF THE |
| OUTSIDE EDGE OF EACH BASIN. THE |
| RECEPTACLE OUTLET SHALL BE LOCATED ON A |
| WALL OR PARTITION THAT IS ADJACENT TO |
| THE BASIN OR BASIN COUNTERTOP. |
| |
| 7)NOTE: PLEASE SEE PLANS INDICATE A "GAS |
| WATER HEATER", YET PANEL SCHEDULE |
| INDICATES ELECTRIC? |
| PLEASE CORRELATE. |
| |
| 8)NOTE: PLEASE SEE "NOTES" #15, MENTIONS |
| 250.60 FOR NEUTRAL/GROUNDING FOR RANGES |
| AND DRYERS. PLEASE SEE THIS ART IS FROM |
| A PREVIOUS CODE. WE ARE NOW UNDER 2002 |
| NEC. THIS IS NOW 250.140 |
| |
| 9)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| SPACING IN BDRM #5 AND DINING RM. |
| |
| 10)NOTE: PLEASE SEE RISER MENTIONS |
| GROUNDING ELECTRODE "OPTIONS". PLEASE |
| SEE 250.50 FOR MIN REQUIRED. FOOTER |
| STEEL AND CWP (IF METAL) IS NOT AN |
| OPTIONAL CONNECTION POINT.PLEASE |
| ADJUST NOTE. |
| |
| 11)NOTE: PLEASE SEE FS 481.025 WHICH |
| REQUIRES PLANS TO BE SIGNED WITH LEGAL |
| SIGNATURE. PLANS APPEAR TO BE "SIGNED" |
| WITH AN INITIAL? IF THIS IS THE LEGAL |
| SIGNATURE, PLEASE PROVIDE A SIGNED, |
| DATED AND SEALED NOTORIZED LETTER TO |
| ATTEST THIS AS YOUR LEGAL SIGNATURE. |
| THIS WILL BE PLACED IN SIGNATURE FILE |
| FOR ANY NEED OF FUTURE REFERENCE. |
| WE HAVE HAD A PROBLEM, WITH PLANS |
| FORGED, SEALS STOLEN ETC. |
| |
| 12)NOTE: PLEASE SEE CODE REFERENCES FOR |
| SD'S ARE FROM THE 1996 NFPA-72. PLEASE |
| SEE WE ARE CURRNETLY UNDER THE 1999 |
| NFPA-72. THESE REFERENCES SHOULD READ |
| 8-1.4.1.6.2, 8-1.4.2 FOR SD |
| REQUIREMENTS |
| |
| PLEASE SEE MOST OF THE ABOVE HAS BEEN |
| REDLINED ON ONE SET OF PLANS FOR AREAS |
| OF NOTES ABOVE. |
| |
| ***PLEASE REMOVE ANY/ ALL OLD VOIDED |
| SHEETS AND INSERT NEW REVISED SHEETS |
| INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| * ADDED NOTE **** |
| |
| PLEASE SEE CIRCUIT FOR WHIRLPOOL TUB |
| SHOWS GFI PROTECTION OPTIONAL? |
| PLEASE SEE 680.71 |