Plan Review Notes For Permit 05011522
Permit Number 05011522
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-12 00:00:00PLUBING PLAN REVIEW FBC 2001 DENIED
 (1)
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
 (2))NOTE: PLANS REQUIRED TO BE SIGNED,
 DATED AND SEALED BY THE ARCHITECT,
 PLEASE SEE FS 481.221 AND FAC 61G1-16
 (3)BACK FLOW PREVENTER REQUIRED, SHOW
 LOCATION OF BACK FLOW PREVENTER.
 (4) PROVIDE ALL INFORMATION ON THE
 OPERATION AND CONTROL OF THE IRRIGATION
 SYSTEM.
 END OF COMMENTS, QUESTIONS 561-805-6692