Plan Review Notes
Plan Review Notes For Permit 05011505
Permit Number 05011505
Review Stop M
Sequence Number 4
Notes
Date Text
2005-07-19 00:00:00DENIED:4TH REQUEST
 ----------------------------------------
 1) SPARE BEDROOMS ON 1ST AND 2ND
 FLOORS (PAGES M1 & M2) SHOW 7" ROUND
 FLEX DUCTS SERVING CLOSETS TO DELIVER 15
 CFM EACH.DUCT IS TOO LARGE FOR THIS
 APPLICATION.THIS DUCT SIZE WILL ALSO
 CAUSE R/A TRANSFER DUCTS TO BE
 UNDERSIZED PER FBC,M 601.4.
  
 2) R/A TRANSFER DUCT IN OFFICE (PAGE M2)
 TO BE MINIMUM 12" ROUND PER FBC,M 601.4.
  
 PLEASE REVISE AND RESUBMIT.
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]