Plan Review Notes For Permit 05011505 |
Permit Number |
05011505 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-07-19 00:00:00 | DENIED:4TH REQUEST | | ---------------------------------------- | | 1) SPARE BEDROOMS ON 1ST AND 2ND | | FLOORS (PAGES M1 & M2) SHOW 7" ROUND | | FLEX DUCTS SERVING CLOSETS TO DELIVER 15 | | CFM EACH.DUCT IS TOO LARGE FOR THIS | | APPLICATION.THIS DUCT SIZE WILL ALSO | | CAUSE R/A TRANSFER DUCTS TO BE | | UNDERSIZED PER FBC,M 601.4. | | | | 2) R/A TRANSFER DUCT IN OFFICE (PAGE M2) | | TO BE MINIMUM 12" ROUND PER FBC,M 601.4. | | | | PLEASE REVISE AND RESUBMIT. | | | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|