Plan Review Notes
Plan Review Notes For Permit 05011505
Permit Number 05011505
Review Stop M
Sequence Number 3
Notes
Date Text
2005-06-28 00:00:00DENIED: 3RD REQUEST
  
 1.PROVIDE DETAIL FOR THE DUCT
 CONNECTION TO AHU LOCATED ON THE FIRST
 FLOOR.PLAN SHEET A2 & M1 INDICATE A
 24" X 24" R/A GRILLE.PLEASE CLARIFY
 DESIGN, CLOSET CANNOT BE USED AS A
 RETURN AIR PLENUM WITH THE DOOR OPENINGS
 INTO THE GARAGE (CARBON MONOXIDE).2001
 FBC(M) 603.9 & 602.
  
 2.PLEASE NOTE RETURN AIR JUMPERS
 SHALL BE SIZED IN ACCORDANCE WITH 2001
 FBC(M)601.4 EXCEPTION #1 & 3.THE
 SECOND FLOOR SPARE BEDROOMS SHALL BE A
 MINIMUM OF 12" AND THE MASTER SUITE
 SHALL BE A MINIMUM OF 14".PLEASE
 REVISE.
  
 3.PLAN SHEET M2 INDICATES RETURN AIR
 BACK TO THE AHU THROUGH A LOUVERED DOOR.
 THE DOOR SCHEDULE ON PLAN SHEET A3, DOOR
 #5TO THE AHU-2 CLOSET INDICATES A
 SOLID CORE DOOR.PLEASE REVISE.
  
 4.PROVIDE AN EQUIPMENT SCHEUDLE AS
 DICTATED BY THE ENERGY CALCULATIONS.
  
 PLEASE NOTE, THE FLOOR PLAN IN THE
 GARAGE AREA ON PLAN SHEET E1 DOES NOT
 CORRELATE WITH A2 & M1 WITH RESPECT TO
 LOCATION OF THE AHU & 80 GAL EWH.
 PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.