Date |
Text |
2005-06-28 00:00:00 | DENIED: 3RD REQUEST |
| |
| 1.PROVIDE DETAIL FOR THE DUCT |
| CONNECTION TO AHU LOCATED ON THE FIRST |
| FLOOR.PLAN SHEET A2 & M1 INDICATE A |
| 24" X 24" R/A GRILLE.PLEASE CLARIFY |
| DESIGN, CLOSET CANNOT BE USED AS A |
| RETURN AIR PLENUM WITH THE DOOR OPENINGS |
| INTO THE GARAGE (CARBON MONOXIDE).2001 |
| FBC(M) 603.9 & 602. |
| |
| 2.PLEASE NOTE RETURN AIR JUMPERS |
| SHALL BE SIZED IN ACCORDANCE WITH 2001 |
| FBC(M)601.4 EXCEPTION #1 & 3.THE |
| SECOND FLOOR SPARE BEDROOMS SHALL BE A |
| MINIMUM OF 12" AND THE MASTER SUITE |
| SHALL BE A MINIMUM OF 14".PLEASE |
| REVISE. |
| |
| 3.PLAN SHEET M2 INDICATES RETURN AIR |
| BACK TO THE AHU THROUGH A LOUVERED DOOR. |
| THE DOOR SCHEDULE ON PLAN SHEET A3, DOOR |
| #5TO THE AHU-2 CLOSET INDICATES A |
| SOLID CORE DOOR.PLEASE REVISE. |
| |
| 4.PROVIDE AN EQUIPMENT SCHEUDLE AS |
| DICTATED BY THE ENERGY CALCULATIONS. |
| |
| PLEASE NOTE, THE FLOOR PLAN IN THE |
| GARAGE AREA ON PLAN SHEET E1 DOES NOT |
| CORRELATE WITH A2 & M1 WITH RESPECT TO |
| LOCATION OF THE AHU & 80 GAL EWH. |
| PLEASE CLARIFY. |
| |