2005-07-01 00:00:00 | DENIED | | | | 1) PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR SIMPSON HETAL 20 AND LUS | | 210 CONNECTORS. | | | | 2) THE TWO HETAL-20 CONNECTORS HAVE A | | UPLIFT CAPACITY OF 2500#. THE UPLIFT | | LISTED IN THE SCHEDULE ON A7, FOR GRF IS | | 4596# AND GRA IS 2782# WHICH EXCEED THE | | CAPACITY OF THE CONNECTORS. PLEASE | | CORRECT. | | | | 3) GIRDER TRUSSES GRE AND GRC SPECIFIED | | ON THE SECOND FLOOR FRAMING PLAN ARE NOT | | LISTED IN THE SCHEDULE ON A7. | | | | 4) FBC 1707.4.4.2 REQUIRES WINDOW AND | | AND DOOR ASSEMBLIES TO BE FASTENED | | THROUGH 1X BUCKS INTO THE STRUCTURAL | | SUBSTRATE. THE NOTES ON THE BUCK DETAILS | | ON A11 SPECIFY ATTACHMENT TO THE 1X | | BUCKS. PLEASE CORRECT. | | | | 5) PROVIDE DETAILS FOR THE BALCONY AND | | STAIR GUARDRAILS SHOWING COMPLIANCE WITH | | FBC 1015 AND 1608.2. | | | | 6) THE TYPICAL STAIR DETAIL ON SHEET A10 | | DOESN'T MATCH STAIRS SHOWN ON PLANS. THE | | UPPER STAIR IS MISSING ONE STEP. THE | | NUMBER OF RISERS AND TREADS IS NOT | | CONSISTENT. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|