Plan Review Notes
Plan Review Notes For Permit 05011505
Permit Number 05011505
Review Stop B
Sequence Number 3
Notes
Date Text
2005-07-01 00:00:00DENIED
  
 1) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR SIMPSON HETAL 20 AND LUS
 210 CONNECTORS.
  
 2) THE TWO HETAL-20 CONNECTORS HAVE A
 UPLIFT CAPACITY OF 2500#. THE UPLIFT
 LISTED IN THE SCHEDULE ON A7, FOR GRF IS
 4596# AND GRA IS 2782# WHICH EXCEED THE
 CAPACITY OF THE CONNECTORS. PLEASE
 CORRECT.
  
 3) GIRDER TRUSSES GRE AND GRC SPECIFIED
 ON THE SECOND FLOOR FRAMING PLAN ARE NOT
 LISTED IN THE SCHEDULE ON A7.
  
 4) FBC 1707.4.4.2 REQUIRES WINDOW AND
 AND DOOR ASSEMBLIES TO BE FASTENED
 THROUGH 1X BUCKS INTO THE STRUCTURAL
 SUBSTRATE. THE NOTES ON THE BUCK DETAILS
 ON A11 SPECIFY ATTACHMENT TO THE 1X
 BUCKS. PLEASE CORRECT.
  
 5) PROVIDE DETAILS FOR THE BALCONY AND
 STAIR GUARDRAILS SHOWING COMPLIANCE WITH
 FBC 1015 AND 1608.2.
  
 6) THE TYPICAL STAIR DETAIL ON SHEET A10
 DOESN'T MATCH STAIRS SHOWN ON PLANS. THE
 UPPER STAIR IS MISSING ONE STEP. THE
 NUMBER OF RISERS AND TREADS IS NOT
 CONSISTENT. PLEASE CORRECT.
  